Advanced Menu; (Advanced) Application And Additional Setup; Auxiliary Heat (Heat Pump Only) Setup; Damper Setup - KMC Controls FlexStat BACnet Operation Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat BACnet:
Table of Contents

Advertisement

Advanced Menu

ADVANCED
APPLICATION
CB PROGRAMS
COMMUNICATION
DATE/TIME
DEVICE
INPUTS
LIMITS
The Advanced Menu displays various submenus.
Not all submenus can be seen on the screen at one
time. Scroll up or down to see additional submenus.
To select the desired submenu, press:
1. Up/Down to move.
2. Enter to select.
NOTE: The Advanced Menu has more submenus
than can appear on the screen at once. Keep
scrolling up or down to see all the options.

(Advanced) Application and Additional Setup

APPLICATION
DEGREES SCALE: °F
APP:
FAN COIL
OPT: 4-PIPE
DAMPER
ADDITIONAL SETUP
FAN
HUMIDITY
MOTION SENSOR
OPTIMUM START
SENSORS
STAGING
To change ° F or C, preprogrammed application type,
and options, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.
Be sure to select the correct °F/°C temperature scale
FIRST! To change the temperature scale after the
application is configured, the selected application
will need to be reset to Not Configured.
NOTE: In Hospitality mode (only), the °F/°C
temperature scale can be toggled by
pressing the Enter button. See (Advanced)
User Interface (UI) Modes on page
The type of application (as well as the model of
FlexStat) affects the context-sensitive options under
Additional Setup.
FlexStat
ADDITIONAL SETUP
19.

Auxiliary Heat (Heat Pump Only) Setup

AUX HEAT SETUP
AUX HEAT:
DELAY (MINS): 60

Damper Setup

ECON:
MODULATING
DCV: ADVANCED
DCV SETUP
MIN POSITION: 0%
CNTRL (0–100%): 2–10 V
ECON ENBLE TEMP: 55° F
LOW LIMIT ALARM: 45° F
NOTE: If the Economizer option is selected when
there is no mixed air temperature sensor
connected, a Low Limit Alarm will result.
See Alarms on page
NOTE: When BAC-1xxxxx models have an
application with the CO
modulating economizer option enabled,
menu items for DCV (Demand Control
Ventilation) will appear. For information
about the DCV options,
CO2 Sensor (and DCV) on page
Fan Setup
SPEEDS:
UNOCC: AUTO
OCC: AUTO
NOTE:
For a Fan Fail Alarm, see Sensor Setup on
page 9 and Alarms on page

Humidity Setup

HUMIDITY SETUP
DEHUMIDIFICATION
HUMIDIFICATION
NOTE: If a dehumidification option is enabled, the
Space Humidity Alarm will also be enabled.
See Alarms on page
7
COMP LOCKOUT
DAMPER SETUP
21.
sensor AND the
2
see (Advanced)
10.
FAN SETUP
CONSTANT SPEED
21.
DEHUMIDIFICATION
DEHUM:
ENABLE
21.
Operation Guide, Rev. L