(Advanced) CB (Control Basic) Programs

CB PROGRAMS
PROG1:
RUNNING
PROG2: RUNNING
SETPOINTS & MODES
PROG3: RUNNING
AUTO-RUN: TRUE
PROG4: RUNNING
CHANGE: READY
PROG5: RUNNING
STATE: RUNNING
PROG6: HALTED
HALT REASON: NORMAL
PROG7: IDLE
HALT DESC:
OUT OF SERVICE: FALSE
To halt or load/run the built-in (1–5) and custom
(6–10) Control Basic programs, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.
If custom Control Basic programs are installed and a
restore to factory settings is performed, all factory
programs are restarted but all custom Control Basic
programs are halted. Change the state of each pro-
gram by loading/running the program from the CB
Programs menu (or BACstage or TotalControl).
If custom Control Basic programs are installed and
set to autorun, whenever the firmware is updated,
ALL (factory and custom) programs are halted. If
custom Control Basic programs are installed but
NOT set to autorun, whenever the firmware is up-
dated, factory programs are restarted but any (manu-
al) running custom programs are halted at restart.
Change the state of each custom program by using
the Update Manager or loading/running each pro-
gram from the CB Programs menu (or BACstage or
TotalControl).
UPDATE MANAGER
PROGRAM CONFIG ERROR
ENABLE FACTORY:
ENABLE CUSTOM: NO
EDIT CB PROGRAMS
DONE
In the About menu, ASV will show CUSTOM if any
built-in Control Basic program (1–5) is not running
or has auto-run disabled. See About the FlexStat on
page
6.
NOTE: Customized programs are the responsibility
of the user. KMC Controls does not provide
support for such programs.
FlexStat
PROGRAM #1
NO
(Advanced) CO
2
CO2 SENSOR
SENSOR INFO
CALIBRATION
CO2 SENSOR INFO
MODEL: T6615
SUB VOL: A15
SW DATE: 090217
S/N: AB00011759
CO2: 873
ELEVATION: 0
STATUS: NORMAL
CO

Sensor Setup and Information

2
NOTE: Set the desired CO
Setpoints menu. See Setpoints on page
To view information about the sensor, set the eleva-
tion, and (depending on model) calibrate the sensor,
press:
1. Up/Down to move among CO
entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.
For maximum sensor accuracy, enter the elevation
(altitude) above sea level of the building's location.
(The default value is 0.) Elevation for any particular
location can be found at such sources as www.earth-
tools.org. (For very tall buildings, the upper floors
would have a higher elevation than lower floors.)
After power is first applied or the FlexStat is restart-
ed, the sensor goes through a warm-up for approxi-
mately half a minute. During the time the sensor
count will be 0 ppm and the Status line will display
WARMUP instead of NORMAL.
The sensor and its firmware are identified by the
model, the compilation subvolume (SUB VOL), com-
pilation date (SW DATE in yymmdd format), and
serial number.
NOTE: With the CO
automatically generated. See (Advanced)
Trend Logs on page
10
Sensor (and DCV)
CO2 CALIBRATION
ELEVATION: 0
REFERENCE GAS: 300
MODE: MONITOR
CO2: 1067
STATUS: NORMAL
CAL TIME: 00:00
setpoint under the
2
Sensor Info
2
sensor enabled, a trend log is
2
19.
Operation Guide, Rev. L