Setpoints

SETPOINTS
COOL SETPT:
HEAT SETPT: 70° F
COOL SETBACK: 80° F
HEAT SETBACK: 64° F
CO2 SETPOINT (PPM): 600
In the Setpoints menu, setpoints and setbacks for
various values are set (The current room temperature
setpoint can also be manually changed from the
Home menu.)
To adjust the setpoints, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Up/Down to increment/decrement value.
NOTE: In firmware version R2.0.0.6, Minimum
Setpoint Differential, was moved to
the Limits menu. See (Advanced)
Temp. Setpoint Limits on page
"Deadband" was separated into Heating
and Cooling Proportional Bands and
moved to the Loops menu. See (Advanced)
PID Loop Configuration on page
FlexStat
74° F
16. Also,
17.

System Setup

SYSTEM ENABLE:
OCC OVRIDE (HRS): 1.0
INACTIVITY (SECS): 60
DISPLAY BLANKING: NO
To adjust the system configuration values, such as
system enable (auto, off, heat, or cool), occupancy
override time, and display inactivity time-out:
1. Up/Down to move among entries.
2. Enter to select.
3. Up/Down to increment/decrement value.
Occupancy Override on this menu is the amount of
time (in hours) a manual change in the setpoint (via
the Up and Down buttons) will be allowed to over-
ride the scheduled setpoint. When the time is set to
0, the override state will last until the next schedule
change.
NOTE: Occupancy override can also be removed
while on the Home screen by pushing the
left button, navigating to OCC, hitting Enter
twice, and changing ON to OFF. See H/C,
Fan, Occupancy, and Override on page
When Display Blanking is enabled (Y), the display
turns off at the same time the backlight goes off
(after reset, initial power-up, or time-out). When any
button is pressed, the display will reappear until the
time-out is reached again.
The menu/display/backlight time-out (seconds
since the last button is pushed) is set in Inactivity.
Access to the Main Menu, setpoint adjust, and
System/Occupancy/Fan override have a default
password level of User. This level can be changed for
each function to None, Operator, or Administrator
through this screen. Passwords are set in the (Ad-
vanced) Passwords menu. See (Advanced) Security
Levels and Passwords on page
23
SYSTEM
AUTO
17.
Operation Guide, Rev. L
4.