(Advanced) Trend Logs; (Advanced) User Interface (Ui) Modes; Mode - KMC Controls FlexStat BACnet Operation Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat BACnet:
Table of Contents

Advertisement

(Advanced) Trend Logs

TREND LOGS
TRUE
TREND 1:
TREND 2: TRUE
TREND 3: FALSE
TREND 4: FALSE
TREND #1
TREND 5: FALSE
SPACE TEMPERATURE LOG
TREND 6: FALSE
OBJECT REF: AI1
TREND 7: FALSE
LOG ENABLE: TRUE
INTERVAL (MINS): 10
STOP W/FULL: FALSE
RESET COUNT: NO
COUNT: 256
TOTAL CNT: 613
VIEW LOG BUFFER
The FlexStat generates default trend logs that are
dependent on options and applications:
• Space temperature (AI1) is the default trend log
#1.
• If AI2 (or AI8) is configured for discharge air
temperature, that will become a default trend
log. See Sensor Setup on page
• Models with CO
sensors (on AI9) will also have
2
a default trend log. See also Damper Setup on
page 7, (Advanced) CO2 Sensor (and DCV) on
page 10, Setpoints on page 23, and DCV (Demand
Control Ventilation) on page
If applicable to the model, the humidity sensor is
AI5 and the motion sensor is BI6, which can also
be user-configured for trend logs. See the FlexStat
Application Guide or relevant FlexStat Installation
Guide for other desired input and output objects in
an application.
To set the desired object to track, press:
1. Up/Down to move among entries.
2. Enter to select.
NOTE: The BACnet standard for log intervals
is hundredths of seconds. The simplified
display on the FlexStat converts the value
to minutes. However, BACstage
TotalControl
®
seconds but in different ways. For a "10"
(minute) interval on a FlexStat display,
TotalControl would show "00:10:00.00"
(hours:minutes:seconds.hundredths of
seconds) and BACstage would show
"60000" (hundredths of seconds) instead.
FlexStat
TL #1–SPACE TEMP
APR17 1:27PM, 71.4
APR17 2:27PM, 71.5
APR17 3:27PM, 71.6
APR17 4:27PM, 71.8
APR17 5:27PM, 76.3
APR17 6:27PM, 81.2
APR17 7:27PM, 82.3
9.
21.
and
do display hundredths of
The trend log buffer may be viewed by scrolling
down and selecting View Log Buffer. The buffer may
also be viewed from the Main Menu by scrolling
down to the Trend Viewer (see page

(Advanced) User Interface (UI) Modes

USER INTERFACE

MODE:

STANDARD
ROTATION VALUES
SHOW TEMP TENTHS: NO
Mode
Mode toggles the home screen and other menus
between the default Standard mode and the (more
restricted) Hospitality and Locked UI modes.
NOTE: COMPLETE ALL OTHER NECESSARY
CONFIGURATION BEFORE SELECTING
HOSPITALITY OR LOCKED UI MODE!
After Hospitality or Locked UI mode is
selected, it is intentionally difficult to
revert to Standard mode!
NOTE: As additional security against
unauthorized bypass of Hospitality or
Locked UI mode from the FlexStat, set
at least an Operator level password. See
(Advanced) Security Levels and Passwords
on page
17.
NOTE: To further configure the FlexStat or
revert to Standard mode, see the FlexStat
Application Guide (downloadable from
the FlexStat product pages after logging in
to the KMC Controls Partner site
partners.kmccontrols.com).
Locked UI mode (also known as Mode 3) appears
like Standard Mode on the Home screen, but all but-
ton functions (except the backlight) are locked.
Hospitality mode (also known as Mode 2) has
limited menus and is typically used in hotel rooms.
Users typically can change only the setpoint, system
mode, and fan speed. Pushing the Left and Right but-
tons displays customizable menu selections (depen-
dent on the configuration), such as System (Auto,
Heat, Cool, and Off) and Fan (Auto, High, Medium).
A three-speed fan displays Auto, Low, Medium, and
High, but a one-speed fan displays Auto and On.
19
24).
USER INTERFACE
MODE:
HOSPITALITY
ROTATION VALUES
SHOW TEMP TENTHS: NO
HOSPITALITY OPTIONS
SETPT CNTRL: SINGLE
https://
Operation Guide, Rev. L