Advanced Menu; (Advanced) Application Options - KMC Controls FlexStat Operation Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat:
Table of Contents

Advertisement

Advanced Menu

ADVANCED
APPLICATION
CB PROGRAMS
COMMUNICATION
DATE/TIME
DEVICE
INPUTS
LIMITS
The Advanced Menu displays various submenus.
Not all submenus can be seen on the screen at one
time. Scroll up or down to see additional submenus.
To select the desired submenu, press:
1. Up/Down to move.
2. Enter to select.
NOTE: The Advanced Menu has more submenus
than can appear on the screen at once. Keep
scrolling up or down to see all the options.

(Advanced) Application Options

APPLICATION
DEGREES SCALE: °F
APP:
FAN COIL
OPT: 4-PIPE
ADDITIONAL SETUP
DAMPER
FAN
HUMIDITY
SENSORS
VALVE
To change ° F or C, preprogrammed application type,
and options, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.
Be sure to select the correct °F/°C temperature scale
first! To change the temperature scale after the
application is configured, the selected application
will need to be reset to Not Configured.
NOTE: In Hospitality mode (only), the °F/°C
temperature scale can be toggled by
pressing the Enter button. See (Advanced)
User Interface (UI) Modes on page
FlexStat
ADDITIONAL SETUP
13.
The type of application (as well as the model of
FlexStat) affects the context-sensitive options under
Additional Setup.
Auxiliary Heat (Heat Pump Only)
AUX HEAT SETUP
AUX HEAT:
DELAY (MINS): 60
Damper Setup
DAMPER SETUP
ECON:
MODULATING
MIN POSITION (%): 10
CNTRL (0–100%): 2–10 V
ECON ENBLE TEMP: 55° F
LOW LIMIT ALARM: 45° F
NOTE: If the Economizer option is selected when
there is no mixed air temperature sensor
connected, a Low Limit Alarm will result.
See Alarms on page
Fan Setup
SPEEDS:
OFF DELAY (SECS): 180
UNOCC: AUTO
OCC: AUTO
NOTE:
For a Fan Fail Alarm, see Sensor Setup on
page 7 and Alarms on page
Humidity Setup
HUMIDITY SETUP
DEHUMIDIFICATION
HUMIDIFICATION
NOTE: If a dehumidification option is enabled, the
Space Humidity Alarm will also be enabled.
See Alarms on page
6
COMP LOCKOUT
13.
FAN SETUP
CONSTANT SPEED
13.
DEHUMIDIFICATION
DEHUM:
ENABLE
ALLOW HTG DEHUM: NO
DEHUM SETPT: 60%RH
DEHUM DEADBAND: 5%RH
13.
Operation Guide, Rev. K