Flexstat Malfunctions After Upgrade - KMC Controls FlexStat BACnet Operation Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat BACnet:
Table of Contents

Advertisement

• Ensure firmware for the correct model is se-
lected in the Firmware Upgrade Tool. If firmware
for the wrong model is accidentally installed, the
outputs will not match the applications/configu-
ration on the display.
NOTE: Backing up the existing settings and
firmware image before or during the
upgrade process (using the Firmware
Upgrade Tool, TotalControl, or BACstage)
is recommended practice.
NOTE: See also the HTO-1103/KMD-5699
Installation Guide, for more information.
(The KMD-5699 product number was
changed to HTO-1103 in August 2010.)
FlexStat

FlexStat Malfunctions After Upgrade

• Check application configuration.
NOTE: Restoring to the factory defaults and
reconfiguring might be needed if how the
FlexStat operates changes. Read all notes
accompanying the firmware update!
NOTE: If custom Control Basic programs are
installed and set to autorun, whenever the
firmware is updated, ALL (factory and
custom) programs are halted. If custom
Control Basic programs are installed
but NOT set to autorun, whenever the
firmware is updated, factory programs
are restarted but any (manual) running
custom programs are halted at restart.
• Change the state of each custom program by
using the Update Manager or loading/running
each program from the CB Programs menu (or
BACstage or TotalControl).
UPDATE MANAGER
PROGRAM CONFIG ERROR
ENABLE FACTORY:
ENABLE CUSTOM: NO
EDIT CB PROGRAMS
DONE
NOTE:
See also Control Basic Programs Do Not
Work on page
NOTE: Customized programs are the responsibility
of the user. KMC Controls does not provide
support for such programs.
35
NO
30.)
Operation Guide, Rev. L