(Advanced) Communications (Bacnet) - KMC Controls FlexStat BACnet Operation Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat BACnet:
Table of Contents

Advertisement

if it is not already at that position. See DCV
(Demand Control Ventilation) on page
VENT OVRIDE (MINS) = Amount of time for
Ventilation Override operation (30 minutes
default). See DCV (Demand Control
Ventilation) on page

(Advanced) Communications (BACnet)

COMMUNICATIONS
ACTIVE:
CONFIGURE
ETHERNET SETTINGS
IP SETTINGS
COMMUNICATIONS
FOREIGN DEV SETTINGS
ACTIVE:
ETHERNET
MS/TP SETTINGS
MAC: 00:D0:6F:89:00:01
COMMUNICATIONS
ACTIVE:
IP
IP ADDRESS: 192.168.1.254
SUBNET MASK: 255.255.0.0
GATEWAY: 255.255.255.255
ACTIVE:
UDP PORT: 47808
IP ADDRESS: 172.16.1.254
UDP PORT: 47808
TIME TO LIVE (SECS): 600
For MS/TP communications, connect the EIA-485
wiring to –A and +B terminals on the backplate (see
the relevant model's installation guide). For Ethernet
IP, and Foreign Device communications (on relevant
"E" models), plug an Ethernet cable directly into the
RJ-45 modular jack on the back of the FlexStat.
To set protocol and parameters for BACnet
communications, select Configure, and then press:
FlexStat
21.
COMMUNICATIONS
FOREIGN DEVICE
COMMUNICATIONS
ACTIVE:
MS/TP
MAC ADDRESS: 1
BAUD RATE: 38400
AUTO-BAUD: OFF
MAX MASTER: 127
21.
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Restart the FlexStat for the new protocol to
become Active. (See the Device menu.)
NOTE: Even if MS/TP is the only option in
firmware R2.0.0.6 and later, Configure must
first be selected before any of the values
can be changed. Otherwise the values are
read only.
Only one protocol can be enabled at any time. The
IP/Ethernet modes do not serve as routers for the
MS/TP connection.
For MS/TP EIA-485 communications, the Max
Master is the highest MAC address a device will
attempt to locate when polling for master devices on
the local network. To avoid possible communication
issues with the network or a computer connected
through a KMD-5576 USB Communicator, the Max
Master number should be the lowest number
needed for that network. To communicate with a
KMD-5576 through the data port at the bottom of
the case, IP/Ethernet-enabled FlexStat models in
one of the Ethernet or IP modes must (temporarily)
be set for MS/TP mode (and restarted). (See
Resetting the FlexStat on page
For IP and IP Foreign Device communications,
consult with the system administrator for the
appropriate settings for the IP Address, Subnet
Mask, Gateway, and UDP Port.
Ethernet communications are essentially plug-and-
play, and the MAC address is not changeable.
14
24.)
Operation Guide, Rev. L