Option 3 - Double EOL Resistors/Single EOL Resistors
This option selects Double EOL resistors (ON) or Single EOL resistors (OFF) wired
as indicated
Single EOL resistors allows the use
of N/C and/or Normally Open contacts.
C
5.6K
NOTES: Option 2 must be set to OFF to enable these options. Default - OFF
Option must be ON for UL Installations.
Option 4 - Test Once a Day Enabled/Disabled
Allows transmission test daily. Default - Disabled.
NOTE: Option must be ON for UL Installations.
Option 5 - Test Once a Week Enabled/Disabled
Allows transmission test weekly. Default - Enabled
NOTE: This option will be overridden If option 4 is set for daily test transmissions.
Option must be OFF for UL Installations.
Option 6 - Enrolled with Connect 24 /Not Enrolled
This option is set automatically during the enrollment procedure with
Connect 24. IF the Skyroute CL3050 is reset to the default settings this option
must be set to ON for the Skyroute CL3050 to resume communications.
Default - Not Enrolled.
Options 7, 8 - System Use
CAUTION: Do NOT change these settings unless it is requested by DSC technical
support personnel. Default - OFF.

[12] Skyroute CL3050 Configuration Options 2

Option 1 - Swinger Shutdown Enabled/Disabled
This option limits the number of alarm events transmitted per zone to 8 until the
counter has been reset (counter automatically resets at midnight), then event
transmissions will resume. Default - Enabled
NOTES: Tampers and Faults will be counted unless they are disabled in section [20].
Option must be OFF for UL Installations.
Options 2 - 8 Future Use

[13] Skyroute CL3050 Trouble Output mask

The PGM output is dedicated for trouble indications. If a control panel is not
monitoring the Skyroute CL3050, an LED or a buzzer can be connected between
this terminal and the RED terminal for a trouble indication. The PGM terminal
switches low from an open-collector state. Connect to the control panel using a
single EOL resistor configuration.
Zx
C
Zx
C
Zx
ohm
5.6K
ohm
5.6K
ohm
Double EOL resistors allows the
zone to be monitored for fault,
tamper, secure and violated condi-
tions. Only Normally Closed contacts
can be used in this configuration
C
Zx
T amper
Contact
5.6K
11
Mode 2, 3
C
Zx
5.6K
5.6K
5.6K
All Modes
All Modes
All Modes
All Modes
Modes 2, 3
All Modes