Zone 3-8 Definitions; Zone 1-2 Loop Response; Skyroute Cl3050 Mode Of Operation - DSC Skyroute CL3050 ver 1.2 Installation & Programming Manual

Universal wireless communicator compatible with all powerseries keypads
Table of Contents

Advertisement

Skyroute CL3050 Universal Wireless Communicator
[02] Zone 3 - 8 Definitions
This allows programming of the six additional zone definitions when operating in
mode 3 with a PC5108 zone expander. See section [01] for details
Default - [01] zones 3 - 8
[03] Zone 1, 2 Loop Response
This entry determines how quickly a zone will respond to changes in state.
NOTE: This does not affect zones on a PC5108 zone expander card.
Default - 05 (0.5 seconds) 01-FF Hex x 0.1 seconds.

[10] Skyroute CL3050 Mode of Operation

[01]
Mode 1 - Bell Follower Operation
Input Voltage
10.6-14 V
AC
Bell Input
TLM Input
System Common
Trouble Output
In this mode, the YEL terminal is connected to the bell output of a control panel.
The Skyroute CL3050 monitors the output for burglary and fire cadences and
transmits the appropriate events. For any type of pulsed cadence, the Skyroute
CL3050 will send a generic Fire event, for any steady bell the Skyroute CL3050
will send a generic Burglary event. The GRN terminal is a trouble input which can
be connected to a system output to alert the Skyroute CL3050 of a system TLM
fault. This will enables the Skyroute CL3050 to be used as a back-up communi-
cator only. If not used, this input must to connected to COM. The bell
cadence will be determined as follows:
Bell must be on for longer then 300mS to be considered a "pulse"
Bell must be on for 3 seconds continuous to be considered "steady"
Bell must be off for 3 seconds continuous to be considered "silenced"
Bell must pulse on and off 3 times to be considered "pulsed", 3rd off-time
will trigger event
NOTE: Mode 1 is not intended for UL Installations.
RED
BLK
YEL
or V
DC
Bell
Pulsed
Steady
GRN COM PGM
RED BLK YEL GRN COM PGM
Alternate connection for
Control Panels where Bell
switches High
Report Code
FA98
BA98
9
NC
Relay
Com
NO
BELL+ BELL-
Group
Fire
Burglary
Mode 3
Modes 2