DSC Skyroute CL3050 ver 1.2 Installation & Programming Manual page 18

Universal wireless communicator compatible with all powerseries keypads
Table of Contents

Advertisement

When the system sees an open circuit across any zone a zone tamper is gener-
ated. DEOL resistors are required for zone tamper reporting. In Section [11],
Option [2] must be set to OFF and Option [3] must be set to ON. In Section [13],
Option [3] must be set to ON and the Skyroute CL3050 must be operating in
mode 2 or 3.
Option 5. Default - OFF, Option 6. Default - OFF
Option 7 - System Maintenance Events
When this option is enabled, the maintenance events enabled in Section [21] are
transmitted using the codes listed in appendix A.
Default - ON,
Option 8 - Generic Zones
The Skyroute CL3050 supports generic and detailed zone alarm reporting. By
default, the Skyroute CL3050 will be in generic zone reporting mode. When in
this mode, all zone types are divided into four reporting groups; BA Burg, FA Fire,
PA Panic, UA Technical. If any zone from this group initiates a transmission, the
generic reporting code for this event is sent, additional violations from other
zones from the same group will be ignored until that group's timer has expired.
See table below for zone type grouping.
Zone
Type
Null
Burglary
Fire
Panic
Technical
Gas*
Heat*
Medical*
Emergency
Water*
Freezer*
Sprinkler*
Hold-up
* Not for UL Listed Installations.
Each zone group has it's own timer. The default time is 5 minutes and is pro-
grammed in Section [23]. If any zone in a group initiates an event, the timer will
start running and the generic event will be sent. If any additional zones from the
same group initiate an event before that group's timer expires, the event will be
ignored. This generic zone reporting mode only applies to zone alarms. Alarm
restorals, tamper/tamper restorals and fault/fault restorals are not grouped
together into generic reporting groups.
The generic identifier will be sent with 98 as it's zone number, this is a special
combination recognized by Connect 24 as a generic event. When the generic
zone reporting toggle is disabled, each zone alarm for each zone type will then
send it's own identifier. Default - ON.
NOTE: The CL3050 communication zone and trouble zone will always send
detailed reporting codes.
Programming Descriptions
Detailed
Reporting Code
-
BA
FA
PA
UA
GA
KA
MA
QA
WA
ZA
SA
HA
14
All Modes
Modes 2, 3
Generic
Reporting Code
-
BA
FA
PA
UA
UA
FA
PA
PA
UA
UA
UA
PA