than 3m, the current density should be less than 3.5A/mm
output of inverter is fully loaded. If the wire longer than 3m, the
current density should be reduced.
A fuse or breaker should be used between battery and inverter, the
value of fuse or switch should be twice of the inverter rated input
current.
Do not connect the battery charger or similar devices to the input
terminal of the inverter.
Do not put the inverter close to the flooded lead-acid battery because
the sparkle in the terminals may ignite the hydrogen released by the
battery.
It‟s an off-grid inverter, if connect to the grid, the inverter may be
damaged.
This inverter can only be used singly, parallel connection or in series
will damage the inverters.
Do not attempt to repair the fault inverter yourself, otherwise it may
lead to a serious accident. Please contact the manufacture‟s engineer.