Protections
Output Short Circuit Protection
The inverter switches off the output immediately when the
connecting load is short. Then it recovers the output automatically
after delaying 5 seconds for the first time, 10 seconds for the second
time, and 15 seconds for the third time. If the short circuit status still
remains when the inverter tries to recover for 3 times, you should
clear the load faults then restart the inverter manually.

Overload Protection

Overload
Character
Continuance
Recover 3 times
If the overload status still remains when the inverter tries to
recover for 3 times, you should reduce the loads then restart the
inverter manually.
Input Low Voltage Protection
The output is switched off when the input voltage is lower than
low voltage protect value, and the output is auto-switched on when
the input voltage reach low voltage recover value. User can also
manually restart the inverter to switch on output by the „ON/OFF
125%
150%
60S
5 seconds for the first time, 10 seconds for the
second time, and 15 seconds for the third time
9
200%
10S
1.5S
>230%
<0.2S