3.1.1
How to start and stop
[Example of a  setting procedure]
Key operated
LED display
MODE


⇔
(1) Start and stop using the operation panel keys (=)
Use the
and
: Motor starts.
To switch between forward run and reverse run from the control panel, the parameter fr
(forward/reverse run selection) needs to be set to 2 or 3.
(2) RUN/STOP by means of an external signal to the terminal board (=):
Sink (Negative) logic
Use external signals to the inverter terminal board to start and stop the motor.
Short
and
CC
Open
and
F
CC
(3) Coast stop
The standard default setting is for slowdown stop. To
make a coast stop, assign a "1(ST)" terminal function
to an idle terminal using the programmable terminal
function.
Change to =.
For coast stop, open the ST-CC when stopping the
motor in the state described at left.The monitor on the
inverter at this time will display .
Displays the operation frequency (operation stopped).
(When standard monitor display selection = [Operation

frequency])
Displays the first basic parameter [History ()].
Press either the
Press ENTER key to display the parameter setting. (Default setting:).

Change the parameter to  (terminal board) by pressing the

Press the ENTER key to save the changed parameter.  and the
parameter set value are displayed alternately.
keys on the operation panel to start and stop the motor.
: Motor stops.
terminals: run forward
terminals: slow down and stop
23
Operation
or
key to select "".
Frequency
F-CC
Motor
speed
F-CC
ST-CC
E6581160
3
key.
Slow down
and stop
ON
OFF
Coast stop
ON
OFF
ON
OFF