6.2.3
Use the UL listed fuses at connecting to power supply.
Short circuit test is performed under the condition of the power supply short-circuit currents in below.
These interrupting capacities and fuse rating currents depend on the applicable motor capacities.
Refer to the table "AIC, Fuse and Wire sizes" in 6.2.3.
Input voltage
200V(1phase)
Up to 2.2kW
Up to 2.2kW
200V(3phase)
4.0kW
5.5kW and over
6
Up to 4.0kW
400V
5.5kW
7.5kW and over
Up to 4.0kW
600V
5.5kW and 7.5kW
11kW and over
Compliance with Peripheral devices
Drive motor
Suitable For Use On A Circuit Capable Of Delivering Not More Than 1,000A rms
Symmetrical Amperes, 240 Volts Maximum When Protected by CC/J Class Fuses.
Suitable For Use On A Circuit Capable Of Delivering Not More Than 5,000A rms
Symmetrical Amperes, 240 Volts Maximum When Protected by CC/J Class Fuses.
Suitable For Use On A Circuit Capable Of Delivering Not More Than 5,000A rms
Symmetrical Amperes, 240 Volts Maximum When Protected by J Class Fuses.
Suitable For Use On A Circuit Capable Of Delivering Not More Than 22,000A rms
Symmetrical Amperes, 240 Volts Maximum When Protected by J Class Fuses.
Suitable For Use On A Circuit Capable Of Delivering Not More Than 5,000A rms
Symmetrical Amperes, 500 Volts Maximum When Protected by CC/J Class Fuses.
Suitable For Use On A Circuit Capable Of Delivering Not More Than 22,000A rms
Symmetrical Amperes, 500 Volts Maximum When Protected by CC/J Class Fuses.
Suitable For Use On A Circuit Capable Of Delivering Not More Than 22,000A rms
Symmetrical Amperes, 500 Volts Maximum When Protected by J Class Fuses.
Suitable For Use On A Circuit Capable Of Delivering Not More Than 5,000A rms
Symmetrical Amperes, 600 Volts Maximum When Protected by J Class Fuses.
Suitable For Use On A Circuit Capable Of Delivering Not More Than 22,000A rms
Symmetrical Amperes, 600 Volts Maximum When Protected by CC/J Class Fuses.
Suitable For Use On A Circuit Capable Of Delivering Not More Than 22,000A rms
Symmetrical Amperes, 600 Volts Maximum When Protected by J Class Fuses.
Power supply short-circuit and maximum input voltage