2-stage Acceleration
2CH
and Deceleration
FRS
Free-run Stop
EXT
External Trip
Unattended Start
USP
Protection
Commercial
CS
source switchover
SFT
Software Lock
Analog Input
AT
Voltage/Current Select
RS
Reset Inverter
PTC thermistor Thermal
PTC
Protection
(C005 only)
Input Function Summary Table
Terminal
Function Name
Symbol
STA
Start
(3-wire interface)
STP
Stop
(3-wire interface)
F/R
FWD, REV
(3-wire interface)
PID
PID Disable
PIDC
PID Reset
UP
Remote Control UP
Function (motorized
speed pot.)
http://www.automatedpt.com
Frequency output uses 2nd-stage acceleration
ON
and deceleration values
Frequency output uses standard acceleration
OFF
and deceleration values
Causes output to turn OFF, allowing motor to free
ON
run (coast) to stop
Output
operates
OFF
deceleration stop motor
When assigned input transitions OFF to ON,
ON
inverter latches trip event and displays
No trip event for ON to OFF, any recorded trip
OFF
events remain in history until reset
On powerup, the inverter will not resume a Run
ON
command (mostly used in the US)
On powerup, the inverter will resume a Run
OFF
command that was active before power loss
power
ON
Motor can be driven by commercial power
OFF
Motor is driven via the inverter
The keypad and remote programming devices
ON
are prevented from changing parameters
OFF
The parameters may be edited and stored
ON
Refer to "Analog Input Settings" on page 3-13.
OFF
The trip condition is reset, the motor output is
ON
turned OFF, and powerup reset is asserted
OFF
Normal power-ON operation
When a thermistor is connected to terminal [5]
and [L], the inverter checks for over-temperature
ANLG
and will cause trip event and turn OFF output to
motor
A disconnect of the thermistor causes a trip
OPEN
event, and the inverter turns OFF the motor
ON
Starts the motor rotation
OFF
No change to present motor status
ON
Stops the motor rotation
OFF
No change to present motor status
ON
Selects the direction of motor rotation: ON = FWD.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction
OFF
Selects the direction of motor rotation: OFF = REV.
While the motor is rotating, a change of F/R will start
a deceleration, followed by a change in direction
ON
Temporarily disables PID loop control. Inverter
output turns OFF as long as PID Enable is active
(A071=01)
OFF
Has no effect on PID loop operation, which operates
normally if PID Enable is active (A071=01)
ON
Resets the PID loop controller. The main
consequence is that the integrator sum is forced to
zero
OFF
No effect on PID controller
ON
Accelerates (increases output frequency) motor from
current frequency
OFF
Output to motor operates normally
72