The [AM] signal offset and gain are adjustable, as indicated below.
Func.
The graph below shows the effect of the gain and offset setting. To calibrate the [AM]
output for your application (analog meter), follow the steps below:
1. Run the motor at the full scale speed, or most common operating speed.
AM output
10V
5V
0
NOTE: As mentioned above, first adjust the offset, and then adjust the gain. Otherwise the
required performance cannot be obtained because of the parallel movement of the offset
adjustment.
CALL NOW 800-985-6929
http://www.automatedpt.com
Description
[AM] output gain
C106
[AM] output offset
C109
a. If the analog meter represents output frequency, adjust offset (C109) first, and then
use
C106
to set the voltage for full scale output.
b. If [AM] represents motor current, adjust offset (C109) first, and then use
the voltage for full scale output. Remember to leave room at the upper end of the
range for increased current when the motor is under heavier loads.
AM output offset adjustment
C109=0~10
Parallel
movement
1/2 FS
http://www.automatedpt.com
Range
0.~255.
0.0~10.0
AM output gain adjustment
AM output
10V
5V
0
Full scale (FS)
Hz or A
45
Email: charles@automatedpt.com
Default
100.
0.0
BC106
C106=0~255
Full scale (FS)
1/2 FS
Hz or A
Email: charles@automatedpt.com
to set