Determining Wire and Fuse Sizes
The maximum motor currents in your application determines the recommended wore size.
The following table gives the wire size in AWG. The "Power Lines" column applies to the
inverter input power, output wires to the motor, the earth ground connection, and any other
components shown in the "Basic System Description" on page 2-7. The "Signal Lines"
column applies to any wire connecting to the two green connectors just inside the front
cover panel.
Motor Output
kW
VT CT VT CT
0.2 0.1
0.4 0.2
0.55 0.4
1.1 0.75 1.5
2.2 1.5
3.0 2.2
0.2 0.1
0.4 0.2
0.75 0.4
1.1 0.75 1.5
2.2 1.5
3.0 2.2
5.5 3.7
7.5 5.5
11
7.5
15
11
18.5 15
0.75 0.4
1.5 0.75
2.2 1.5
3.0 2.2
4.0 3.0
5.5 4.0
7.5 5.5
11
7.5
15
11
18.5 15
Note 1: Field wiring must be made by a UL-Listed and CSA-certified closed-loop terminal
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66ft. (20m).
Note 4: Use 18 AWG / 0.75mm
CALL NOW 800-985-6929
http://www.automatedpt.com
HP
Inverter Model
WJ200-001SF
¼
1/8
WJ200-002SF
½
¼
WJ200-004SF
¾
½
1
WJ200-007SF
WJ200-015SF
3
2
WJ200-022SF
4
3
WJ200-001LF
¼
1/8
WJ200-002LF
½
¼
WJ200-004LF
1
½
WJ200-007LF
1
WJ200-015LF
3
2
WJ200-022LF
4
3
WJ200-037LF
7.5
5
WJ200-055LF
10
7.5
WJ200-075LF
15
10
WJ200-110LF
20
15
WJ200-150LF
25
20
1
½
WJ200-004HF
WJ200-007HF
2
1
WJ200-015HF
3
2
4
3
WJ200-022HF
WJ200-030HF
5
4
WJ200-040HF
7.5
5
WJ200-055HF
10
7.5
15
10
WJ200-075HF
WJ200-110HF
20
15
WJ200-150HF
25
20
connector sized for the wire gauge involved. Connector must be fixed by using
the crimping tool specified by the connector manufacturer.
terminals).
http://www.automatedpt.com
Wiring
Power Lines
Signal Lines
2
AWG16 / 1.3mm
(75°C only)
2
AWG12 / 3.3mm
(75°C only)
2
AWG10 / 5.3mm
2
AWG16 / 1.3mm
2
AWG14 / 2.1mm
(75°C only)
2
AWG12 / 3.3mm
(75°C only)
2
AWG10 / 5.3mm
18 to 28
(75°C only)
AWG / 0.14
2
AWG6 / 13mm
to 0.75 mm
(75°C only)
shielded wire
2
AWG4 / 21mm
(see Note 4)
(75°C only)
2
AWG2 / 34mm
(75°C only)
2
AWG16 / 1.3mm
2
AWG14 / 2.1mm
2
AWG12 / 3.3mm
(75°C only)
2
AWG10/ 5.3mm
(75°C only)
2
AWG6 / 13mm
(75°C only)
2
AWG6 / 13mm
(75°C only)
2
wire for the alarm signal wire ([AL0], [AL1], [AL2]
10
Email: charles@automatedpt.com
Applicable
equipment
Fuse (UL-rated,
class J, 600V ,
Maximum
allowable current)
10A
20A
30A
10A
15A
20A
30A
2
60A
80A
80A
10A
15A
30A
50A
50A
Email: charles@automatedpt.com