Hitachi WJ200 Series Quick Reference Manual page 36

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
Unattended Start Protection
If the Run command is already set when power is turned ON, the inverter starts running
immediately after powerup. The Unattended Start Protection (USP) function prevents that
automatic startup, so that the inverter will not run without outside intervention. When USP
is active and you need to reset an alarm and resume running, either turn the Run
command OFF, or perform a reset operation by the terminal [RS] input or the keypad
Stop/reset key.
In the figure below, the [USP] feature is enabled. When the inverter power turns ON, the
motor does not start, even though the Run command is already active. Instead, it enters
the USP trip state, and displays
the alarm by turning OFF the Run command per this example (or applying a reset). Then
the Run command can turn ON again and start the inverter output.
Run command [FW,RV] 1
Inverter output frequency
Option
Code
13
Valid for inputs:
Required settings
Notes:
Note that when a USP error occurs and it is
canceled by a reset from a [RS] terminal input, the
inverter restarts running immediately.
Even when the trip state is canceled by turning
the terminal [RS] ON and OFF after an under
voltage protection
will be performed.
When the running command is active
immediately after the power is turned ON, a USP
error will occur. When this function is used, wait
for at least three (3) seconds after the powerup to
generate a Run command.
CALL NOW 800-985-6929
http://www.automatedpt.com
0
[USP] terminal 1
0
Alarm output terminal 1
0
0
Inverter power supply 1
0
Events:
Terminal
Function Name
Symbol
USP
Unattended Start
Protection
C001~C007
(none)
E09
occurs, the USP function
http://www.automatedpt.com
E 13
error code. This requires outside intervention to reset
Alarm
E13
cleared
command
State
ON
On powerup, the inverter will not resume a Run
command (mostly used in the US)
OFF
On powerup, the inverter will resume a Run
command that was active before power loss
Example (default input configuration shown for
–FE and –FU models; –F models require input
configuration—see
7
6
See I/O specs on
34
Email: charles@automatedpt.com
Run
Description
page
3–49):
USP
5
4
3
2
1
L
PLC
PCS
page 4–6.
Email: charles@automatedpt.com
t
P24

Hide quick links: