Hitachi WJ200 Series Quick Reference Manual page 69

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
Func.
Code
[AM] terminal selection
C028
(Analog voltage output
Digital current monitor
C030
reference value
Output [11] active state
C031
Output [12] active state
C032
Alarm relay active state
C036
Output mode of low current
C038
detection
Low current detection level
C039
Output mode of overload
C040
warning
Overload warning level
C041
Overload warning level, 2
C241
motor
Frequency arrival setting
C042
for acceleration
Frequency arrival setting
C043
for deceleration
PID deviation level
C044
Frequency arrival setting 2
C045
for acceleration
Frequency arrival setting 2
C046
for deceleration
CALL NOW 800-985-6929
http://www.automatedpt.com
"C" Function
Name
11 programmable functions:
00...Output frequency
0...10V)
01...Output current
02...Output torque
04...Output voltage
05...Input power
06...Electronic thermal load ratio
07...LAD frequency
10...Heat sink temperature
11...Output torque (with code)
13...General output
16...Option
Current with digital current monitor
output at 1,440Hz
Range is 20%~200% of rated
current
Select logic conversion, two option
codes:
00...normally open [NO]
01...normally closed [NC]
Two option codes:
00...During acceleration,
deceleration and constant speed
01...During constant speed only
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
Two option codes:
00...During accel., decel. and
constant speed
01...During constant speed only
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
nd
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
Sets the allowable PID loop error
magnitude (absolute value),
SP-PV, range is 0.0 to 100%
Set range is 0.0 to 400.0 Hz
Set range is 0.0 to 400.0 Hz
http://www.automatedpt.com
Run
Mode
Description
Edit
67
Email: charles@automatedpt.com
Defaults
Lnitial data
Units
07
[LAD]
Rated current
A
00
00
-
01
01
INV rated
A
current
01
Rated current
A
x 1.15
Rated current
A
x 1.15
0.0
Hz
0.0
Hz
3.0
%
0.00
Hz
0.00
Hz