Monitoring functions
NOTE:. Mark " " in b031=10 shows the accessible parameters when b031 is set "10", high
level access.
Func.
Code
D001
D002
D003
D004
D005
D006
CALL NOW 800-985-6929
http://www.automatedpt.com
"d" Function
Name
Output frequency monitor
Output current monitor
Rotation direction monitor
Process variable (PV),
PID feedback monitor
Intelligent input
terminal status
Intelligent output
terminal status
http://www.automatedpt.com
Description
Real time display of output frequency
to motor from
0.0 to 400.0Hz
If b163 is set high, output frequency
(F001) can be changed by up/down
key with d001 monitoring.
Filtered display of output current to
motor, range is
0 to 655.3 ampere (~99.9 ampere for
1.5kW and less)
Three different indications:
"F" ...Forward
"o" ...Stop
"r" ...Reverse
Displays the scaled PID process
variable (feedback) value (A075 is
scale factor),
0.00 to 10000
Displays the state of the intelligent
input terminals:
7
6 5 4
3
2
1
Terminal numbers
Displays the state of the intelligent
output terminals:
Relay
12 11
46