Two Stage Acceleration and Deceleration
When terminal [2CH] is turned ON, the inverter
changes
deceleration from the initial settings
F003) to use the second set of acceleration/
deceleration values. When the terminal is
turned OFF, the inverter is returned to the
original acceleration and deceleration time
(F002
deceleration time 1). Use
time 2) and
the second stage acceleration and deceleration
times.
In the graph shown above, the [2CH] becomes active during the initial acceleration. This
causes the inverter to switch from using acceleration 1 (F002) to acceleration 2 (A092).
Option
Code
09
Valid for inputs:
Required settings
Notes:
Function
stage acceleration. It must be set =
the input terminal method in order for the [2CH]
terminal assignment to operate.
CALL NOW 800-985-6929
http://www.automatedpt.com
the
rate
of
acceleration
acceleration
time
A092
A093
(deceleration time 2) to set
Terminal
Function Name
Symbol
2CH
Two-stage Accelera-
tion and
Deceleration
C001~C007
A092, A093,
A094=00
A094
selects the method for second
00
http://www.automatedpt.com
and
(F002
and
Output
frequency
[2CH]
1,
and
F003
(acceleration
[FW,RV]
State
ON
Frequency output uses 2nd-stage acceleration and
deceleration values
OFF
Frequency output uses the initial acceleration 1 and
deceleration 1 values
Example (default input configuration shown—see
page
3–49):
7
6
to select
See I/O specs on
33
Email: charles@automatedpt.com
Target
frequency
second
initial
1
0
1
0
Description
2CH
5
4
3
2
1
L
PLC
PCS
page 4–6.