Hitachi WJ200 Series Quick Reference Manual page 32

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
CAUTION: Be sure to diode in between "P24" and "PLC" when connecting plural
inverters with digital input wiring in common.
The power to the inverter control part can be supplied externally as shown below. Except
driving motor, it is possible read and write the parameters by keypad and via
communication even the drive itself is not powered.
By having ability inverter doesn't block the current flowing into itself when it is not
powered. This may cause the closed circuit when two or more inverters are connected to
common I/O wiring as shown below to result in unexpected turning the on the input. To
avoid this closed circuit, please put the diode (rated:50V/0.1A) in the path as described
below.
CALL NOW 800-985-6929
http://www.automatedpt.com
Short
Power ON
bar
P24
PLC
L
Input
ON
1
Short
Power OFF
bar
P24
PLC
L
1
Switch
OFF
In case of Source logic
P24
Short
PLC
bar
L
Input
ON
1
P24
PLC
L
Short
bar
1
Switch
OFF
http://www.automatedpt.com
Inserting
diode
Switch
OFF
Switch
OFF
30
Email: charles@automatedpt.com
Power ON
P24
PLC
L
Input
OFF
1
Power OFF
P24
PLC
L
1
P24
PLC
L
Input
OFF
1
P24
PLC
L
1
Email: charles@automatedpt.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents