Hitachi WJ200 Series Quick Reference Manual page 59

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929
Func.
Code
PID sleep function action
a156
threshold
PID sleep function action delay
a157
time
[VR] input active range start
A161
frequency
[VR] input active range end
A162
frequency
[VR] input active range start %
A163
[VR] input active range end %
A164
[VR] input start frequency
A165
select
CALL NOW 800-985-6929
http://www.automatedpt.com
"A" Function
Name
Sets the threshold for the action,
set range 0.0~400.0 Hz
Sets the delay time for the
action, set range 0.0~25.5 sec
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
The starting point (offset) for the
current input range,
range is 0. to 100.%
The ending point (offset) for the
current input range,
range is 0. to 100.%
Two options; select codes:
00...Use offset (A161 value)
01...Use 0Hz
http://www.automatedpt.com
Run
Mode
Description
Edit
57
Email: charles@automatedpt.com
Defaults
Lnitial data
Units
0.00
Hz
0.0
sec
0.00
Hz
0.00
Hz
0.
%
100.
%
01
Email: charles@automatedpt.com

Hide quick links:

Advertisement

Table of Contents