Table 2.8:Jp12 Do Power On Configuration; Figure 2.6:Isolated Digital Output Connection - Advantech UNO-2050G User Manual

Lx800 500mhz automation computer with 2 x lan, 2 x rs-232, 2 x isolated rs-232/422/485,16 x isolated di/o
Table of Contents

Advertisement

Table 2.8: JP12 DO Power On Configuration
JP12
Isolated Outputs
Each of isolated output channels comes equipped with a Darlington tran-
sistor. All eight output channels share common collectors and integral
suppression diodes for inductive loads.
Please note that if an external voltage (5 ~ 40 V
lated output channel while it is being used as an output channel, the cur-
rent will flow from the external voltage source to the UNO-2050G. Please
take care that the current through each DO pin not exceed 200 mA.
Figure 2-6 shows how to connect an external output load to the UNO-
2050G's isolated outputs.
Please note that DO6 and DO7 may be configured as Counter 0 and
Counter 1's output pins, please refer to "Section 2.6" for detail.
R
Figure 2.6: Isolated Digital Output Connection
UNO-2050G User Manual
Power on Configuration after Hot Reset
Default configuration
Keep last status after hot reset
ISO 5V
R
Internal
R
R
R
14
) is applied to an iso-
DC
External
COM
IDO0....7
Load0....7
IGND
V
DC
5~40V
DC
E1

Advertisement

Table of Contents
loading