Maintenance and Troubleshooting
4.0 Maintenance and Troubleshooting
The following information is provided to help you keep your RD-E Series inverter/charger in
optimum operational condition.
4.1
Recommended Inverter and Battery Care
The RD-E Series inverter/charger is designed to provide you with years of trouble-free service.
Even though there are no user-serviceable parts, it is recommended that every 6 months you
perform the following maintenance steps to ensure optimum performance and extend the life of
your batteries.
WARNING: Prior to performing the following checks, switch OFF both the AC and
DC circuits.
•
Visually inspect the batteries for cracks, leaks, or swelling – replace if necessary.
•
Use baking soda to clean and remove any electrolyte spills or buildups.
•
Check and tighten all battery holddown clamps (if applicable).
•
Clean and tighten all battery terminals and connecting cables
[10 to 12 ft lbf (13.6 to 16.3 N-m)].
•
Check and fi ll battery water levels (Liquid Lead Acid batteries only).
•
Check individual battery voltages (load test those that have a voltage difference of more
than 0.3 VDC from each other) – replace if necessary.
•
Check all cable runs for signs of chafi ng – replace if necessary.
•
Check the inverter's cooling vents – clean as necessary.
•
Check and tighten the inverter's internal AC terminal block connections
[16 in lbf (1.8 N-m)].
Page 37
© 2010 Magnum Energy, Inc