Write Setting Data - Omron E5ZN Operation Manual

Hide thumbs Also See for E5ZN:
Table of Contents

Advertisement

Commands and Responses
5-9-5

Write Setting Data

Command
Response
74
Variable
MRC
SRC
type
"01"
"02"
Variable
Address
type
"C1"
"0000" to "0019"
"0100" to "0119"
"C3"
"0000" to "002E"
"0100" to "012E"
"C5"
"0000"
"0100"
"C7"
"0000" to "0001"
"0100" to "0101'
This command writes setting data. If the number of elements is set between
"2" and "6", consecutive address setting data can be written.
For details on addressing, refer to 5-10 Variable Area Map .
This command can be used in setting area 1 only. If the Temperature Control-
ler is in setting area 0 when the command is received, it returns an error.
Before executing the command, use operation commands to enable commu-
nications writing.
To save the operation/adjustment level setting data to internal non-volatile
memory, use the "write mode" operation command to set the write mode to
"backup." If it is not set to backup mode, the setting data will not be stored
when the power is turned OFF. Refer to 6-3 Setup Level Configuration and
Front Panel Keys for details on the operation/adjustment level.
MRC
SRC
Response code
"01"
"02"
"0000"
Response code: The code shown above represents normal completion. For
details on the response code, refer to 5-6 Write to Variable Area .
Bit
No. of
Address
position
elements
"00"
"0001"
ch
1
2
1
2
1
2
1
2
Section 5-9
Data
Setting data (setting area 1)
Setting data
Description
Setting data for setting area 0
Setting data for setting area 1
Setting data for setting area 0
Setting data for setting area 1