Fuzzy self-tuning temperature controller with advanced pid (2 pid) contr (33 pages)
Summary of Contents for Omron E5 N-H Series
Page 1
Digital Temperature Controllers/Digital Controllers E5@N/E5@N-H Upgraded 1/16, 1/8, and 1/4 DIN Controllers, the Best-selling E5@N Series. Basic Type (Renewal E5@N) and Advanced Type (New E5@N-H). • Improved indication accuracy and preventive maintenance (Basic Type E5@N). • New high-performance Controllers (Advanced Type E5@N-H). •...
Contents Digital Temperature Controllers E5CN/E5CN-U ..........E5AN/E5EN ..........Digital Controllers E5CN-H............E5AN-H/E5EN-H.......... Operation Procedure • Operation ............. Common to All Controllers • Safety Precautions ........CX-Thermo Support Software • EST2-2C-MV4..........
Basic-type Digital Temperature Controller E5CN/E5CN-U (48 x 48 mm) New 48 x 48-mm Basic Temperature Controller with Enhanced Functions and Performance. Improved Indication Accuracy and Preventive Maintenance Function. • Indication Accuracy Thermocouple input: ±0.3% of PV (previous models: ±0.5%) Pt input: ±0.2% of PV (previous models: ±0.5%) 48 ×...
Page 4
E5CN/E5CN-U Lineup 0 or 2 auxiliary outputs 1 control output Temperature input 2 control outputs 2 auxiliary outputs Terminal block 0 or 2 auxiliary outputs 1 control output Analog input E5CN 2 control outputs 2 auxiliary outputs Basic Type 0, 1, or 2 auxiliary 1 control output Temperature input outputs...
Page 5
E5CN/E5CN-U Ordering Information Controllers with Terminal Blocks Power supply Size Case color Input type Auxiliary outputs Control output 1 Model voltage Relay output E5CN-RMT-500 None Voltage output (for driving SSR) E5CN-QMT-500 Current output E5CN-CMT-500 Thermocouple or 100 to 240 VAC Resistance Relay output E5CN-R2MT-500...
Page 6
E5CN/E5CN-U Model Number Structure Model Number Legend (Plug-in-type Controllers) E5CN-@@@U 1 2 3 4 1. Output Type 3. Input Type R: Relay output T: Universal thermocouple/platinum resistance thermometer Q: Voltage output (for driving SSR) L: Analog Input C: Current output 4.
Page 7
E5CN/E5CN-U Accessories (Order Separately) USB-Serial Conversion Cable Adapter Model Connectable models Model E58-CIFQ1 Terminal block models Y92F-45 Note: Use this Adapter when the panel has been previously prepared Terminal Cover for the E5B@. Connectable models Terminal block models Sockets (for Plug-in Models) Model E53-COV17 Type...
Page 8
E5CN/E5CN-U Specifications Ratings No D in model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage 100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA) E5CN Power 24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA)
Page 9
E5CN/E5CN-U Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal Inputs) Input Platinum resistance Infrared temperature Analog Thermocouple Type thermometer sensor input 60 to 0 to 10 to Name Pt100 JPt100 70°C 50 mV °C °C °C 2300 2300 1800 1800 1700 1700 1700 1600 1500...
Page 10
E5CN/E5CN-U Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent.
Page 11
✽6. External communications (RS-485) and cable communications for the Setup Tool can be used at the same time. ✽7. The E5CN-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11 is not certified for UL listing.
Page 12
E5CN/E5CN-U USB-Serial Conversion Cable Current Transformer (Order Separately) Ratings Applicable OS Windows 2000, XP, or Vista Thermo Mini, CX-Thermo version 4.0 or Dielectric strength 1,000 VAC for 1 min Applicable software higher Vibration resistance 50 Hz, 98 m/s E5AN/E5EN/E5CN/E5CN-U/E5AN-H/ E54-CT1: Approx. 11.5 g, E54-CT3: Approx. Applicable models Weight E5EN-H/E5CN-H...
Page 13
(If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current.) • Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose. E5CN...
Page 14
E5CN/E5CN-U Nomenclature E5CN Temperature unit E5CN-U The front panel is the same for the E5CN and E5CN-U. No.1 display Operation indicators No. 2 display Up Key Level Key Mode Key Down Key Dimensions (Unit: mm) E5CN Panel Cutout Terminal Models Mounted Separately Group Mounted +1.0...
Page 15
IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. 48.8 Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required.
Page 16
E5CN/E5CN-U Adapter Y92F-45 Note: Use this Adapter when the panel has already been prepared for the E5B@. Fixture (Accessory) 69.6 to 77.6 72 × 72 67 × 67 Mounted to E5CN Panel (1 to 8 mm) 72 × 72 48 × 48 77.3 (to back of E5CN) E5CN-U Wiring Socket Front-connecting Socket...
Basic-type Digital Temperature Controller E5AN/E5EN (96 x 96 mm and 48 x 96 mm) New 96 x 96-mm and 48 x 96-mm Basic Temperature Controllers with Enhanced Functions and Performance. Improved Indication Accuracy and Preventive Maintenance Function. • Indication Accuracy Thermocouple input: ±0.3% of PV (previous models: ±0.5%) Pt input: ±0.2% of PV (previous models: ±0.5%) Analog input: ±0.2% FS (previous models: ±0.5%)
Page 18
E5AN/E5EN Lineup 3 auxiliary outputs 1 control output Temperature input 2 control outputs 3 auxiliary outputs E5AN/E5EN Terminal block Basic Type 1 control output 3 auxiliary outputs Analog input 2 control outputs 3 auxiliary outputs Note: Models with one control output or two control outputs can be used for heating/cooling control. Model Number Structure Model Number Legend Controllers...
Page 19
E5AN/E5EN Ordering Information E5AN Controllers with Terminal Blocks Functions Power Auxilia- Case Control output Size supply Input type Model Heater Power supply Control color voltage outputs burnout for Sensor output 2 Relay output E5AN-R3MT-500-N Voltage output E5AN-Q3MT-500-N (for driving SSR) Current output E5AN-C3MT-500-N Relay output...
Page 20
E5AN/E5EN E5EN Controllers with Terminal Blocks Functions Power Auxilia- Case Control Size supply Input type Model Heater Power supply Control color output 1 voltage outputs burnout for Sensor output 2 Relay output E5EN-R3MT-500-N Voltage output E5EN-Q3MT-500-N (for driving SSR) Current output E5EN-C3MT-500-N Relay output E5EN-R3HMT-500-N...
Page 21
E5AN/E5EN Option Units Name Function Model RS-232C communications E53-EN01 Communications Unit RS-485 communications E53-EN03 Event Input Unit Event inputs E53-AKB Accessories (Order Separately) USB-Serial Conversion Cable Current Transformers (CTs) Model Hole diameter Model E58-CIFQ1 5.8 dia. E54-CT1 12.0 dia. E54-CT3 Terminal Cover CX-Thermo Support Software Connectable models...
Page 22
E5AN/E5EN Specifications Ratings No D in model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power 100 to 240 VAC: 10 VA consumption 24 VAC/VDC: 5.5 VA (24 VAC)/4 W (24 VDC) Models with temperature inputs...
Page 23
E5AN/E5EN Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Input Platinum resistance Infrared temperature Analog Thermocouple type thermometer sensor input 60 to 0 to 10 to Name Pt100 JPt100 70°C 50 mV °C °C °C 2300 2300 1800 1800 1700 1700 1700 1600 1500...
Page 24
E5AN/E5EN Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent.
Page 25
E5AN/E5EN Characteristics Thermocouple: (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1 Platinum resistance thermometer: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit max. Indication accuracy Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max.
Page 26
E5AN/E5EN USB-Serial Conversion Cable Current Transformer (Order Separately) Ratings Applicable OS Windows 2000, XP, or Vista Thermo Mini, CX-Thermo version Dielectric strength 1,000 VAC for 1 min Applicable software 4.0 or higher Vibration resistance 50 Hz, 98 m/s E5AN/E5EN/E5CN/E5CN-U/E5AN- E54-CT1: Approx. 11.5 g, Applicable models Weight H/E5EN-H/E5CN-H...
Page 27
The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit. • Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose. Controllers Option Units •...
Page 28
E5AN/E5EN Nomenclature E5AN E5EN Temperature unit Operation indicators SUB1 SUB2 SUB1 SUB3 SUB2 No.1 display SUB3 Temperature unit Operation indicators No.1 display No. 2 display No.2 display OUT1 STOP OUT1 STOP No.3 display No. 3 display Operation indicators OUT2 MANU OUT2 MANU Up Key...
Page 29
E5AN/E5EN E5EN Mounted Separately Group Mounted +1.0 (48 × number of units − 2.5) +0.6 79.2 +0.8 Group mounting does not 120 min. allow waterproofing. +0.8 Terminal Cover (E53-COV16) Waterproof Mounting Bracket (Accessory) Packing (Accessory) (Accessory) Crimp terminal size: M3.5 •...
Page 30
IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.)
Advanced Digital Temperature Controller E5CN-H (48 x 48 mm) A New High-performance Controller: High Resolution, High Speed, and High Input Accuracy. Logic Operations and Preventive Maintenance Function. • High-resolution display with 5 digits/0.01°C display in a compact Controller (48 x 48 mm). •...
Page 32
E5CN-H Lineup 1 control output 2 auxiliary outputs E5CN-H Terminal block Fully universal input Advanced Type 2 control outputs 2 auxiliary outputs Note: Models with one control output and models with two control outputs can be used for heating/cooling control. Model Number Structure Model Number Legend Controllers...
Page 33
E5CN-H Ordering Information Controllers Size Case Color Power supply voltage Auxiliary output Control output 1 Model Relay output E5CN-HR2M-500 Voltage output (for driving SSR) E5CN-HQ2M-500 100 to 240 VAC Current output E5CN-HC2M-500 Linear voltage output E5CN-HV2M-500 Black Relay output E5CN-HR2MD-500 Voltage output (for driving SSR) E5CN-HQ2MD-500 24 VAC/VDC...
Page 34
E5CN-H Specifications Ratings No D in model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage 100 to 240 VAC: 8.5 VA (max.) (E5CN-HR2 at 100 VAC: 3.0 VA) Power consumption 24 VAC/VDC: 5.5 VA (24 VAC)/3.5 W (24 VDC) (max.) (E5CN-HR2D at 24 VAC: 2.7 VA) Any of the following can be selected (i.e., fully universal input).
Page 35
E5CN-H Input Ranges Thermocouple/Platinum Resistance Thermometer/Analog Input (Fully Universal Inputs) Platinum resistance Analog Input type Thermocouple thermometer input 1 to 0 to 0 to 4 to 0 to Name Pt100 JPt100 PL II 20 mA 20 mA 10 V 2300.0 2300 1800.0 1800...
Page 36
E5CN-H Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent.
Page 37
E5CN-H Characteristics Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1 Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max. Indication accuracy Analog input: ±0.1% FS ±1 digit max. CT input: ±5% FS ±1 digit max.
Page 38
E5CN-H USB-Serial Conversion Cable Current Transformer (Order Separately) Ratings Applicable OS Windows 2000, XP, or Vista Thermo Mini, CX-Thermo version Dielectric strength 1,000 VAC for 1 min Applicable software 4.0 or higher Vibration resistance 50 Hz, 98 m/s E5AN/E5EN/E5CN/E5CN-U/ E54-CT1: Approx. 11.5 g, Applicable models Weight E5AN-H/E5EN-H/E5CN-H...
Page 39
E5CN-H External Connections • A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current.
Page 40
E5CN-H Nomenclature E5CN-H Temperature unit SUB1 SUB2 No. 1 display SUB3 Operation indicators OUT1 STOP No. 2 display OUT2 CWM MANU Up Key Level Key E5CN-H Mode Key Down Key Dimensions (Unit: mm) E5CN-H Panel Cutout Mounted Separately Group Mounted +1.0 (48 ×...
Page 41
IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. 48.8 Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.) The Waterproof Packing does not need to be attached if a waterproof structure is not required.
Page 42
E5CN-H Adapter Y92F-45 Note: Use this Adapter when the panel has already been prepared for the E5B@. Fixture (Accessory) 69.6 to 77.6 72 × 72 67 × 67 Mounted to E5CN-H Panel (1 to 8 mm) 72 × 72 48 × 48 77.3 (to back of E5CN-H)
Advanced Digital Temperature Controller E5AN-H/E5EN-H (96 x 96 mm and 48 x 96 mm) A New High-performance Controller: High Resolution, High Speed, and High Input Accuracy. Logic Operations and Preventive Maintenance Function. Plus Infrared Port on Front Panel. • High-resolution display with 5 digits/0.01×C display. •...
Page 44
E5AN-H/E5EN-H Lineup 1 control output 2 auxiliary outputs E5AN-H/E5EN-H Terminal block Fully universal input Advanced Type 2 control outputs 2 auxiliary outputs Note: The Controller can be used for heating/cooling control even if only 1 control output is used. Model Number Structure Model Number Legend Controllers Option Units...
Page 45
E5AN-H/E5EN-H Ordering Information E5AN-H Optional functions Power Case Control Auxiliary Heater Size supply Control output 1/2 Model Event Transfer color method output burnout voltage inputs output 4 to 20-mA Control Output Unit × 2 E5AN-HAA2HBM-500 input 4 to 20-mA SSR outputs × 2 E5AN-HSS2HBM-500 input 4 to 20-mA...
Page 46
E5AN-H/E5EN-H E5EN-H Optional Functions Power Auxil- Heater Case Control Size supply iary Control output 1/2 burn- Model Event Transfer color method voltage output inputs output 4 to 20-mA Control Output Unit × 2 E5EN-HAA2HBM-500 input 4 to 20-mA SSR outputs × 2 E5EN-HSS2HBM-500 input 4 to 20-mA...
Page 47
E5AN-H/E5EN-H Specifications Ratings No D in model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage 100 to 240 VAC: 12 VA Power consumption 24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC) Any of the following can be selected.
Page 48
E5AN-H/E5EN-H Input Ranges Thermocouple/Platinum Resistance Thermometer (Fully Universal Inputs) Input Platinum resistance Thermocouple Analog input type thermometer 4 to 0 to 1 to 0 to 0 to Name Pt100 JPt100 20 m 20 m 10 V 2300.0 2300 1800.0 1800 1700.01700.0 1700 1600...
Page 49
E5AN-H/E5EN-H Alarm Outputs Each alarm can be independently set to one of the following 15 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent.
Page 50
E5AN-H/E5EN-H Characteristics Thermocouple: (±0.1% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1 Platinum resistance thermometer: (±0.1% of indicated value or ±0.5°C, whichever is greater) ±1 digit max. Analog input: ±0.1% FS ±1 digit max. Indication accuracy CT input: ±5% FS ±1 digit max.
Page 51
E5AN-H/E5EN-H USB-Serial Conversion Cable Current Transformer (Order Separately) Ratings Applicable OS Windows 2000, XP, or Vista Thermo Mini, CX-Thermo version Dielectric strength 1,000 VAC for 1 min Applicable software 4.0 or higher Vibration resistance 50 Hz, 98 m/s E5AN/E5EN/E5CN/E5CN-U/ Weight E54-CT1: Approx.
Page 52
E5AN-H/E5EN-H Electrical Life Expectancy Curve for SSR Outputs (OUT1/OUT2) Ratings • Rated load voltage: 75 to 250 VAC Relays (Reference Values) • Rated load current: 1 A (resistive load) Note: 1. The load current must be within the derating curve. 2.
Page 53
E5AN-H/E5EN-H External Connections • A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured temperature values as a result of leakage current.
Page 54
E5AN-H/E5EN-H Nomenclature E5AN-H E5EN-H Temperature unit Operation indicators SUB1 SUB2 SUB1 SUB3 SUB2 No.1 display SUB3 Temperature unit Operation indicators No.1 display No.2 display No.2 display OUT1 RSP STOP OUT1 STOP No.3 display No.3 display Operation indicators OUT2 MANU OUT2 MANU Up Key Mode Key...
Page 55
E5AN-H/E5EN-H E5EN-H Mounted Separately Group Mounted✽ +1.0 (48 × number of units − 2.5) +0.6 +0.8 Group mounting does not 120 min. allow waterproofing. • Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between +0.8 Controllers.)
Page 56
E5AN-H/E5EN-H Accessories (Order Separately) USB-Infrared Conversion Cable E58-CIFIR USB-Infrared Conversion Cable (2,000) 35.8 4.6 dia. USB connector (type A plug) LED indicator: RD LED indicator: SD 17.8 With Mounting Adapter Connected Mounting Adapter 18.5 Mounting Adapter (Accessory) 99.2 23.1 21.8 (75) USB-Serial Conversion Cable E58-CIFQ1...
Page 57
IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider one year a rough standard. OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement.)
E5@N/E5@N-H Operation Setting Levels Diagram This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level.
Page 59
E5@N/E5@N-H Advanced Type Power ON Start in manual mode. Start in automatic mode. Press the O Key or the PF Key for at least 1 s. ✽4 Press the O+ Adjustment M Keys for at Operation Press Level least 1 s. Level the O + Press the...
Page 60
E5@N/E5@N-H Parameters Basic Type Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN/E5AN/E5EN Digital PF Key ✽2 Temperature Controllers User's Manual Basic Type Power ON (Cat. No. H156). Starting in manual mode.
Page 61
E5@N/E5@N-H Monitor/Setting Item Level (E5AN/E5EN only) Monitor/Setting Monitor/Setting Monitor/Setting Monitor/Setting Monitor/Setting Item Display 1 Item Display 3 Item Display 4 Item Display 5 Item Display 2 Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level). Press the O Key for at least 1 s.
Page 62
E5@N/E5@N-H Advanced Type Some parameters are not displayed depending on the model of the Controller and parameter settings. For details, refer to the E5CN-H/E5AN-H/ Power ON E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157). Manual Control Level Operation Adjustment PID Setting Bank Setting...
Page 63
E5@N/E5@N-H Power ON Starting in manual mode. Manual Control Level Press the O 25.0 Starting in Press the PF Key Control Key or the PF automatic for at least 1 s. 100.0 only Key for at least mode. ✽1 1 s. ✽1 PV/MV Press the O and M Keys for...
Page 64
E5@N/E5@N-H Press the O Key for at least 1 s. Press the O Key for at least 3 s. Other than the Auto/Manual Switch display Initial Setting Level Press the O Key less than 1 s. Press the O Key less than 1 s. in-t Communications Protect Level...
Page 65
E5@N/E5@N-H Power ON Manual Control Level Operation Adjustment PID Setting Monitor/Setting Bank Setting Protect Level Level Item Level Level Level Level Communica- Initial Setting tions Setting Level Level Advanced Function Setting Level Press the O Key for at least 1 s. Advanced Function Setting Level pfd1 istp...
E5@N/E5@N-H Safety Precautions !CAUTION When inserting the body of the Temperature Controller into the case, confirm that the hooks on the top and bottom are securely engaged with the case. If the body of Do not touch the terminals while power is being supplied. the Temperature Controller is not inserted properly, faulty Doing so may occasionally result in minor injury due to contact in the terminal section or reduced water...
Page 67
E5@N/E5@N-H 11.When executing self-tuning, turn ON power to the load (e.g., the temperature, the longer the service life. Therefore, the service heater) at the same time as or before supplying power to the life can be extended by lowering the temperature of the product.
Page 68
E5@N/E5@N-H Mounting Mounting the Terminal Cover Mounting to a Panel E5CN For waterproof mounting, waterproof packing must be installed on the Make sure that the “UP” mark is facing up, and then attach the E53- Controller. Waterproofing is not possible when group mounting COV17 Terminal Cover to the holes on the top and bottom of the several Controllers.
Page 69
E5@N/E5@N-H E5AN/E5EN Tool insertion hole Tool insertion hole E5AN E5EN 1. Insert a flat-blade screwdriver into the two tool insertion holes (one on the top and one on the bottom) to release the hooks. 2. Insert the flat-blade screwdriver in the gap between the front panel and rear case (two on the top and two on the bottom), and use it to pry and pull out the front panel slightly.
CX-Thermo Support Software Ver. 4.0 EST2-2C-MV4 Monitoring/Setting Support Software for E5CN/CN-H, E5AN/AN-H, E5EN/EN-H, E5ZN, E5@R/@R-T, and EJ1 Temperature Controllers Enabling Faster Parameter Setup, Device Adjustment, and Maintenance • Enables editing and batch-downloading parameters from a personal computer, reducing the work required to set parameters. Usability is improved with table-formatted parameter editing from version.
Page 72
CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE...
Need help?
Do you have a question about the E5 N-H Series and is the answer not in the manual?
Questions and answers