Using the Event Input

4-5

Using the Event Input

4-5-1

Setting the Event Input

Number of
multi-SP uses
0
1
4-5-2

Using Control Start (RUN)/Control Stop (STOP)

4-5-3

Using the Multi-SP

Using the Event Input
48
The event input, which uses an external contact input, is set using the "No. of
multi-SP uses" and "event input assignment" settings.
The multi-SP function is allocated for event input by setting the "No. of multi-
SP uses" parameter. The RUN/STOP control function is set using the "event
input allocation" parameter.
When the event input is not used as a multi-SP function, the multi-SP function
can be used via host communications or the E5ZN-SDL Setting Display Unit
by setting the "multi-SP use" parameter.
The following table shows the relationship between the three settings.
Settings
Event input
allocation
None
RUN/STOP
None
RUN/STOP
The shaded areas indicate the default values for the "No. of multi-SP uses,"
"event input allocation," and "multi-SP use" parameters.
The three communications parameters given in the left columns of the above
table are given priority in the following order: "No. of multi-SP uses," "event
input allocation," and "multi-SP use."
When the "No. of Multi-SP uses" parameter is set to 0 and the event input allo-
cation is set to "RUN/STOP," the RUN/STOP function can be controlled using
the event input. The following table shows the relationship between event
input contact status and control status.
Event input contact
ON (closed)
OFF (open)
The multi-SP function is used to switch between two set points. Different set
points are set in advance for set point 0 and set point 1 and the event input
contact signals or E5ZN-SDL Setting Display Unit is used to switch them.
The set points listed in the following table can be selected by turning ON and
OFF the event input.
Event input contact
OFF (open)
ON (short)
Note
1.
Switch event inputs during communications with the host computer.
ON/OFF is detected for inputs of 50 ms or more.
2.
Set points for ch1 and ch2 are both switched using event input.
Function allocated
to event input
Multi-SP use
ON
None
OFF
ON
RUN/STOP
OFF
ON
Multi-SP from event
input
OFF
ON
OFF
Control status
RUN
STOP
Set point
Set point 0
Set point 1
Section 4-5
Changing multi-SP via host
communications or Setting
Display Unit
Possible
Not possible
Possible
Not possible
Not possible