Variable Area Map
Variable
Address
type
C3
000B
1
000C
000D
000E
-
000F
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
90
ch
Setting data name
Alarm 1 type
Alarm 2 type
Alarm 3 type
Control output 1 alloca-
tion
Control output 2 alloca-
tion
Auxiliary output 1 alloca-
tion
Auxiliary output 2 alloca-
tion
Operation after power ON 00000000H (0):
Communications data
length
Communications stop bit
Communications parity
Communications
response transmission
wait time
No. of multi-SP uses
Event input function
Use multi-SP
00000000H (0):
No alarm function
00000001H (1):
Upper and lower limit alarm
00000002H (2):
Upper limit alarm
00000003H (3):
Lower limit alarm
00000004H (4):
Upper and lower limit range alarm
00000005H (5):
Upper and lower limit alarm with standby
sequence
00000006H (6):
Upper limit alarm with standby sequence
00000007H (7):
Lower limit alarm with standby sequence
00000008H (8):
Absolute value upper limit alarm
00000009H (9):
Absolute value lower limit alarm
0000000AH (10): Absolute value upper limit alarm with
standby sequence
0000000BH (11): Absolute value lower limit alarm with standby
sequence
Same as for alarm 1 type
Same as for alarm 1 type
00000000H (0):
Heating control output for ch1
00000001H (1):
Cooling control output for heating/cooling
control for ch1
00000002H (2):
Alarm 1 and HB alarm OR output for ch1
00000003H (3):
Alarm 2 output for ch1
00000004H (4):
Alarm 3 output for ch1
00000005H (5):
Heating control output for ch2
00000006H (6):
Cooling control output for heating/cooling
control for ch2
00000007H (7):
Alarm 1 and HB alarm OR output for ch2
00000008H (8):
Alarm 2 output for ch2
00000009H (9):
Alarm 3 output for ch2
Same as for control output 1 allocation
Same as for control output 1 allocation
Same as for control output 1 allocation
Stop
00000001H (1):
Continue (Continues the operation status
from before the power supply was stopped.)
00000007H (7): 7
00000008H (8): 8
00000001H (1): 1
00000002H (2): 2
00000000H (0): None
00000001H (1): Even
00000002H (2): Odd
00000000H to 0000270FH (0 to 9,999)
00000000H (0): No multi-SP
00000001H (1): Switch between SP0/1
00000000H (0): Non
00000001H (1): RUN/STOP
00000000H (0): OFF
00000001H (1): ON
Section 5-10
Description