Variable Area Map
Variable
Address
type
C3
011A
2
011B
-
011C
2
011D
011E
2
011F
0120
0121
0122
-
0123
0124
2
0125
-
0126
2
0127
0128
0129
-
012A
012B
2
012C
012D
012E
-
C5
0000
1
0100
2
94
ch
Setting data name
SP ramp setting
Standby sequence
restart
Alarm 1 open for alarm
Alarm 1 hysteresis
Alarm 2 open for alarm
Alarm 2 hysteresis
Alarm 3 open for alarm
Alarm 3 hysteresis
Use heater burnout
Heater burnout latch
Heater burnout hystere-
sis
a
MV upper limit value
MV lower limit value
Input digital filter
Additional PV display
Temperature input offset
display add
Alarm 1 latch
Alarm 2 latch
Alarm 3 latch
Cold junction compensa-
tion method
Remote PV
Remote PV
00000000H (0): OFF
00000001H to 0000270FH (1 to 9,999)
00000000H (0): Condition A
00000001H (1): Condition B
00000000H (0): Closed
00000001H (1): Open
00000001H to 0000270FH (0.1 to 999.9)
00000000H (0): Closed
00000001H (1): Open
00000001H to 0000270FH (0.1 to 999.9)
00000000H (0): Closed
00000001H (1): Open
00000001H to 0000270FH (0.1 to 999.9)
00000000H (0): OFF
00000001H (1): ON
00000000H (0): OFF
00000001H (1): ON
00000001H to 000001F4H (0.1 to 50.0)
00000000H to 00000064H (0.00 to 1.00)
Standard: Manipulated variable lower limit + 0.1 to 0000041AH
(manipulated variable lower limit + 0.1 to 105.0)
Heating/cooling: 00000000H to 0000041AH (0.0 to 105.0)
Standard: FFFFFFCEH to manipulated variable upper limit -
0.1 (-5.0 to manipulated variable upper limit - 0.1)
Heating/cooling: FFFFFBE6H to 00000000H (105.0 to 0.0)
00000000H to 0000270FH (0.0 to 999.9)
00000000H (0): OFF
00000001H (1): ON
00000000H (0): OFF
00000001H (1): ON
00000000H (0): OFF
00000001H (1): ON
00000000H (0): OFF
00000001H (1): ON
00000000H (0): OFF
00000001H (1): ON
00000000H (0): OFF
00000001H (1): ON
Temperature: According to specified range for each sensor
Analog:
Scaling lower limit - 5% FS to scaling upper limit + 5% FS
Temperature: According to specified range for each sensor
Analog:
Scaling lower limit - 5% FS to scaling upper limit + 5% FS