Westerbeke 7.0 KW BGC -60Hz Technical Manual page 132

Marine gasoline generator sets
Table of Contents

Advertisement

Trouble
No ignition, cranks,
does not start. (continued)
Starts, stops when
ON switch released.
Engine stops.
Westerbeke Generators
Possible Cause
5. Coil faulty .
6. Distributor faulty.
7. Wiring faulty.
1. Safety circuit
switch or wiring
faulty.
2. Fuse blown.
3. Overs peed module
faulty.
1. Low oil pressure or
overheated.
2. Low oil pressure
switch fails to
close.
3. High water or
exhaust temperature
switches open at too
Iowa temperature.
4. Overspeed module.
5. Switch and wiring.
128
Remedy
5. Check coil.
6. Check distributor, points,
condenser, cap and wires.
7. Check wires and con-
nections for shorts,
breaks and corrosion.
1. Inspect all wiring for
shorts, corrosion or
loose connections.
Check operation of
switches.
2. Check fuses.
3. Check module.
Do bypass test.
2. Check oil, fresh water
and raw water cooling.
2. Check for satisfactory
operation with switch
bypassed.
3. Same as above.
4. Check engine speed.
Check module for pro-
per operation.
5. Inspect all wiring for
loose connections and
short circuits.