11

Finishing

A. Mantel Projections
Figure 11.1 shows the minimum vertical and corresponding
maximum horizontal dimensions of appliance mantels or other
combustible projections above the top front edge of the appliance.
Note: All measurements in inches.
SPACE
16-1/4 IN.
Figure 11.1
Clearances to Mantels or other Combustibles
above Appliance
Top View
MANTEL
LEG
Figure 11.2
Mantel Leg or Wall Projections
(Acceptable on both sides of opening.)
B. Facing Requirements
There are two options to finish the front facing on the fireplace,
outside fit surround and inside fit surround.
COMBUSTIBLE
SHEATHING
AIR
HEADER BOARD
12
11
10
9
8
7
6
5
4
6-5/16 IN.
3
2
7-3/4 IN.
1
2-3/4 IN.
FROM BOTTOM OF HOOD
(VISIBLE WITH DOOR REMOVED)
1 in.
½ Inch
Heat & Glo • Crescent II • 2083-902 Rev. G • 9/05
Outside Fit Surround
The outside fit surround design is used for facing
materials less than 3/4 inch for combustibles, and less
than one inch for noncombustibles. The surround is
designed to fit flush on finishing materials. Heat & Glo
recommends using our cabinets or 1/2 inch finishing
materials (see Figure 11.3).
Adjust fireplace position if facing material is other than
CEILING
1/2 inch thick.
For Outside Fit Surrounds
• Surface temperatures are hot around fireplace
opening.
27 IN.
• Finishes may discolor or peel if not suited to
temperatures above 200
13-3/4 IN.
Figure 11.3
To cut the arch use the dimensions shown in Figure 11.4.
Figure 11.4
CAUTION
0
F.
Outside Fit Surround
30-7/16 IN.
22-7/8 IN.
Outside Facing Dimensions
31