A. Facing Material
• Metal front faces may be covered with non-combustible
materials only.
• Facing and/or finishing materials must not interfere with
air flow through or removal of decorative fronts or access
for service.
• Facing and/or finishing materials must never overhang
into the glass opening.
• Observe all clearances when applying combustible
materials.
• Seal joints between the finished wall and appliance top
and sides using a 300 ºF minimum sealant. Refer to
Figure 10.1.
WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specified in
this manual. Overlapping materials could ignite and will
interfere with air flow through decorative fronts.
NOTICE: Surface temperatures around the appliance will
become warm while the appliance is in operation. Ensure
finishing materials used for all surfaces (floor, walls,
mantels, etc.) will withstand temperatures up to 190°F.
FACING MATERIAL UP TO 1/2 IN. THICK
MAY BE COMBUSTIBLE - TOP AND SIDES
0 IN.
1 IN.
0 IN.
HIGH TEMPERATURE (300 ºF/ 149 ºC MIN.)
TOP AND SIDE SEAL JOINT
BOTTOM 1 INCH (SHADED AREA)
MAY BE COVERED WITH COMBUSTIBLE
OR NON-COMBUSTIBLE MATERIAL
Figure 10.1 Facing Materials
54
0 IN.
Heat & Glo • 6000C-IFT, 8000C-IFT Installation Manual • 2502-980 Rev. M • 3/21
FACTORY-INSTALLED NON-COMBUSTIBLE BOARD
DO NOT REMOVE
A
inches
6000
millimeters
inches
8000
millimeters
Figure 10.2 Noncombustible Facing Diagram
B
A
B
39-3/4
41
1010
1041
41-3/4
48
1060
1219