AXIS A1001 Network Door Controller & AXIS Entry Manager

System Configuration

To delete and reconfigure the hardware configuration, click Reset and start new hardware configuration.
Locks
1. If a door monitor will be used, select Door monitor and then select the option that matches how the door monitor
circuits will be connected.
2. If the door lock shall lock immediately after the door has been opened, select Lock when door opens.
3. Specify the door monitor time options, or if no door monitor will be used, the lock time options.
The following options for door monitors, door monitor time and lock time are available:
Door monitor
Open circuit = Open door – The door monitor gives the door open signal when the circuit is open. Select if the
-
door monitor circuit is normally closed.
Open circuit = Closed door – The door monitor gives the door closed signal when the circuit is open. Select if
-
the door monitor circuit is normally open.
Lock when door opens – Select if the door shall lock immediately after the door has been opened. When the door
closes, the door locks without delay.
Access time – Set the number of seconds the door shall remain unlocked after access has been granted. The door remains
unlocked until the door has been opened and will lock when it closes regardless of whether the access time has expired or
not. If the door remains unopened, it locks when the set access time has been reached.
Open too long time – Set the number of seconds the door is allowed to stay open. If the door is still open when the
open too long time has been reached, the door open too long alarm is triggered. Set up an action rule to configure which
action the open too long event shall trigger.
Pre-alarm time – A pre-alarm is a warning signal that is triggered before the open too long time has been reached. It
tells the administrator and, depending on how the action rule has been set up, it can also warn the user (the person
entering the door) that the door needs to be closed or the real alarm, the door open too long alarm, will go off. Set the
number of seconds before the door open too long alarm is triggered the system shall give the pre-alarm warning signal.
To disable the pre-alarm, set the pre-alarm time to 0.
Door unlocked time – Deselect Door monitor to make this option available. Set the number of seconds the door shall
remain unlocked after access has been granted. The door remains unlocked until the door has been opened and will
lock when it closes regardless of whether the door unlocked time has expired or not. If the door remains unopened, it
locks when the set door unlock time has been reached.
Pre-lock signal time – Deselect Door monitor to make this option available. A pre-lock signal is a warning signal that is
triggered before the door locks. It tells the administrator and, depending on how the action rule has been set up, it can also
warn the user (the person entering the door) that the door will lock soon. Set the number of seconds before the door
locks the system shall give the pre-lock warning signal. The pre-lock signal time must be shorter than the door unlocked
time. To disable the pre-lock warning signal, set the pre-lock signal time to 0.
For information about how to set up an action rule, see Setting Up an Action Rule, on page 29.
The following options for locks are available:
12 V
-
Locked = GND (-) – Select for locks that remain locked during power outages (fail close/secure).
-
Locked = 12 V – Select for locks that unlock during power outages (fail open/safe).
Relay – Can only be used on one lock per door controller. If two doors are connected to the door controller, a relay can
only be used on the lock of the second door.
-
Locked = Relay open – Select for locks that remain locked when the relay is open (fail close/secure).