Installation (for qualified installers only)
Clearances
Due to the high temperature of the heater, it should be located out of traffic and away from furniture and
draperies.
Side
Wall
k
Mantel Clearances
T The maximum mantel depth is 12".
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it
does, it is considered a mantel and must meet the mantel requirements listed in this manual.
Above Base of Insert (n)
© Travis Industries
n
m
l
37+"
36"
35"
Mantel Height
34"
33"
32"
31"
Minimum Clearances
Sidewall to Insert
k
Side Facing
l
Top Facing*
m
Mantel*
n
Extension onto Hearth
x
* The non-combustible top facing must extend
35-1/2" above the base of the insert or to the
bottom of the mantel (whichever is less).
** Measured from the base of the insert.
x
Maximum Mantel Depth
0" 1" 2" 3" 4" 5" 6" 7" 8" 9" 10" 11" 12"
4100322
4"
4"
35-1/2"**
35-1/2"**
1-1/4"
100-01237_000