Installation (for qualified installers only)

Vent Requirements

The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent
gas appliance must use it's own separate vent system.
Make sure the exhaust pipe on the heater connects to the exhaust portion of the cap. The
illustrations below show how the flex liners should be attached.
The exhaust vent must reline the entire length of the chimney and terminate above the chimney top
Be careful not to crimp or rupture the liner when bending it into chimney offsets
When installed, the vent must meet all of the vent manufacturer's requirements
Make sure to use the following:
4" UL 441 or 1777 Gas Liner for Exhaust, 3" UL 441 or 1777 Gas Liner for Air Inlet
Simpson Duravent 6-5/8" to 3" & 4" Co-Linear Adapter and Flashing (Travis Part # 98900124).
Simpson Duravent High-Wind Vertical Termination Cap

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 6,000 feet (1,800 M). In this testing
we have found that the heater, with its standard orifice, burns correctly with just an air shutter
adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety
hazard. Consult your dealer or installer if you suspect an improperly adjusted air shutter.
© Travis Industries
Exhaust
(4" dia.)
Max. Ht. 40'
Min. Ht. 8'
4100322
Inlet
(3" dia.)
Max. 2'
offset
13
100-01237_000