In the US:
a) less than 3 feet above any forced air inlet located within 10 feet;
b) less than 4 feet below or horizontally from, or one foot above, any door, window or gravity air
inlet into any building;
c) less than two feet from an adjacent building and not less than 7 feet above grade when located
adjacent to a public walkway. Mobile home installations must use a spark arrester. Other restrictions
may apply, such as the need to maintain a minimum distance to a gas meter. See NFPA 211.

b) Vertically with new chimney system

(Refer to Figure 13)
NOTE: Follow vent chimney manufacturer's instructions.
OPTION: To achieve a centered vertical installation, a 45º elbow and a clean-out tee can be used to offset
the pipe from the exhaust outlet to the rear center of the stove.
OPTION: Install vent elbow in place of clean-out tee. Locate stove. Drop plumb bob to center of tee outlet,
mark point on ceiling. Install ceiling support and vent pipe per vent manufacturer's instructions.
FIGURE 12
Venting through wall
Basement installation