4.4 Monitoring Inputs

A NetAXS™ panel supports door, panel, and auxiliary inputs. The door inputs provide egress and
tamper status, the panel inputs provide power fail and tamper status, and the auxiliary inputs support
any downstream status.
Click
Status > Inputs
Figure 4-5: Status > Inputs
The Input Status screen enables you to:
• View the current status of each input (Normal, Alarm, Trouble, Cut, Short, Shunted).
• Shunt or un-shunt any input. When an input is shunted, the alarm is de-activated. This is a way
• Restore the input to its configured time zone. A time zone is a specified time period during
NetAXS™ Access Control Unit User's Guide, Document 800-00233, Revision A
to display the Input Status screen:
you can allow the input to grant access without falsely signalling an alarm. The default state of
an input point is "un-shunted."
which the input will be shunted and the alarm de-activated. (see
Management" on page 15).
Monitoring NetAXS™ Status

Monitoring Inputs

"Configuring Time
4-7