3: Conventional Initiation Circuits; Class B Inputs; Class A Inputs - Honeywell Silent knight 5895XL Installation And Operation Manual

Intelligent power module
Hide thumbs Also See for Silent knight 5895XL:
Table of Contents

Advertisement

Hardware Installation
2.
Configure the circuit for Class A in programming.
NOTE: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
Figure 3.13 uses both I/O circuit 5 and 6, so in programming it would be referred to as point 5.
3.5.3 Conventional Initiation Circuits
This section of the manual explains how to install conventional initiating devices for Class A (Style D) or Class B (Style B) configura-
tions.

Class B Inputs

You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL
panel.
To install a Class B switch:
1.
Wire the Class B switch as shown in Figure 3.14.
2.
Configure the circuit through programming (see FACP Installation Manual).

Class A Inputs

You can connect conventional Class A switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL
panel.
24
Figure 3.13 Class A Notification Appliance Circuit Configuration
UL Listed EOL
4.7 k
Figure 3.14 Class B Input Switches
Regulated
5895XL Manual - P/N 151142-L8:L 08/09/2017
Flexputs™ I/O Circuits