Flexput I/O Circuits
3.8.3 Conventional Initiation Circuits
This Section of the manual explains how to install the conventional initiating devices for Class A or Class B configurations.

Class B Inputs

Connect conventional Class B switches, such as waterflow switches and pull stations, directly to the I/O circuits of the RPS-1000 panel.
To install a Class B switch, wire the switch as shown in Figure 3.12 and configure the circuit through FACP programming.
UL listed EOL
4.7 kΩ

Class A Inputs

Connect conventional Class A switches, such as waterflow switches and pull stations, directly to the I/O circuits of the RPS-1000 panel.
To install a Class A switch, wire the switch as shown in Figure 3.13 and configure the circuit through FACP programming.
NOTE: In programming, any point that uses the multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
since Figure 3.13 uses both I/O circuit 5 and 6, it would be referred to as point 5.
RPS-1000 Manual — P/N 151153:R 2/15/2022
15
14
13
12
11
10
0
X
0
X
0
X
I / 0 1
I / 0 2
I / 0 3
Figure 3.12 Class B Input Switches
15
14
13
12
11
0
X
0
X
0
I / 0 1
I / 0 2
I / 0 3
point pairs
Note: I/O circuit 5 and 6 are
used as an example. Any I/O
point pairing can be used.
Figure 3.13 Class A Initiating Switches
9
8
7
6
5
4
0
X
0
X
0
X
I / 0 4
I / 0 5
I / 0 6
10
9
8
7
6
5
X
0
X
0
X
0
I / 0 4
I / 0 5
I / 0 6
4
X
Installation
33