Adding A New Netaxs™ Panel; Creating The Panel With Quick Start Wizard; Figure 3-1: Quick Start Wizard - Panel Screen - Honeywell NetAXS User Manual

Access control unit
Table of Contents

Advertisement

Configuring via WIN-PAK
Adding a New NetAXS™ Panel
3.2 Adding a New NetAXS™ Panel
To add a NetAXS panel, first create the panel in the WIN-PAK Quick Start Wizard, and then complete
the configuration manually with the WIN-PAK Panel Configuration screen.

3.2.1 Creating the Panel with Quick Start Wizard

Add a new panel by selecting its Loop and configuring the following from the Quick Start Wizard
Panel screen:
• Panel type (Select N1000-4X/PW2000-4X from the dropdown list)
• Panel name (Loop[Loop number]-Panel [Panel address]
• Panel address (Select from the dropdown list)

Figure 3-1: Quick Start Wizard - Panel Screen

Each panel on a communication loop must have a unique address. The address must correspond
Note:
with the address that is set by DIP switches on the panel.
After adding the NetAXS panel via the QSW, you must update the Reader and Input interlocks to
match them with the default wiring of the NetAXS panel. Proceed to
Manually" on page 3 and make the necessary changes.
3-2
www.honeywell.com
The NetAXW Gateway panel's baud rate is set configured via the NetAXS web server (see the
NetAXS Access Control Unit Installation Guide for instructions). When you set the Loop Type
in the QSW to 485 ACK-NAK, you define the baud rate to be 19.2 kilobits per second. This
baud rate and the panel's baud rate must match to communicate properly. For WIN-PAK SE or
WIN-PAK PE systems, you can adjust the baud rate of the N-485 device to 115 kilobits per
second for optimum performance.
"Configuring the Panel

Hide quick links: