SRX240 Services Gateway Grounding Specifications

Related
Documentation
Copyright © 2013, Juniper Networks, Inc.
Appendix B: SRX240 Services Gateway Power Guidelines, Requirements, and Specifications
Connecting the SRX240 Services Gateway DC Power Supply Model to a DC Power
Source on page 50
To meet safety and electromagnetic interference (EMI) requirements and to ensure
proper operation, the services gateway must be adequately grounded before power is
connected. A grounding lug available on the rear of the services gateway chassis is used
to connect the device to earth ground.
WARNING:
Before device installation begins, a licensed electrician must
attach a cable lug to the grounding and power cables that you supply. A cable
with an incorrectly attached lug can damage the device (for example, by
causing a short circuit).
To ground the device before connecting power, you connect the grounding cable to earth
ground and then attach the lug on the cable to the chassis grounding point with the
screw.
Table 41 on page 147
lists the specifications of the grounding cable used with the device.
Table 41: Grounding Cable Specifications for the Services Gateway
Grounding Requirement
Grounding cable
Amperage of grounding cable
Grounding lug
SRX240 Services Gateway Site Electrical Wiring Guidelines on page 143
Grounding the SRX240 Services Gateway on page 55
SRX240 Services Gateway AC Power Specifications and Requirements on page 145
SRX240 Services Gateway Power Supply on page 20
Specification
14 AWG single-strand wire cable
Up to 25 A
Ring-type, vinyl-insulated TV14-6R lug or
equivalent
147