6.20.8 Reset to Default Settings

Press the MENU key to access the menu data screens and press the 'down' arrow key to
scroll to the original factory 'default settings' adjustment screen display:
Press the F1 key to display the following active adjustment screen:
When the ENTER key is pressed the following factory defaults are reset:
Press the MENU key to abandon the operation and return to the menu data screen.
6.21

Overload Operation

When the UPS is operating and an overload condition is first detected, the following
"Overload Warning" screen is displayed.
After a period of time, if the overload is still not reduced and the STOP/RUN key switch is
in the RUN position, the UPS will automatically transfer to Bypass. If the overload condition
is still present, the following screen will be displayed:
If the STOP/RUN key switch is in the STOP position; the UPS is in the Bypass Mode and,
if the overload condition is still present, the following screen will be displayed:
64
MENU DATA RESET
DATA INITIALIZATION
>F1: TO ACCESS RESET
>∆/∇:PRV/NEXT SCREEN
MENU DATA RESET
DATA INITIALIZATION
> MENU: NO DATA RESET
>ENTER: ACCEPT CHANGE
1) Resets the voltage-reference setting to +0
2) Resets the buzzer volume to 'loud'
3) Resets the serial station address to 31h
4) Resets the idle mode to 3 minutes
- UPS ON-LINE -
OUTPUT VOLTAGE= ###V
OUTPUT CURRENT= ###%
* UPS OL: REDUCE LOAD *
- BYPASS OPERATION -
OUTPUT VOLTAGE=208
CURRENT= 114/116/114%
* UPS OL: REDUCE LOAD *
- BYPASS OPERATION -
OUTPUT VOLTAGE=208
CURRENT= 114/116/114%
* UPS OL: REDUCE LOAD *
4200FA Installation and Operation Manual