3.0 Installation Precautions

Based on the 4200FA UPS external dimensions and the way the outer panels are removed; minimum
amounts of unobstructed space around the unit are necessary for ventilation and maintenance
access. The following section and Fig. 3.1 shows the minimum clearances required for proper UPS
site installation.
3.1

Equipment Placement

1) Do not install the UPS on an inclined surface,
or areas that are subject to frequent vibrations
or jolting. This could damage UPS circuits.
2) Do not allow liquids or foreign objects to get
inside the UPS.
3) Allow at least the following spacing for air
ventilation and maintenance access.
Front: 20 in. (500 mm)
Sides: 6 in. (152 mm)
Back:
15/25/30kVA Premium - 6 in. (152 mm)
15-30kVA Base - 12 in. (304 mm)
50kVA Premium - 12 in. (304 mm)
25/50kVA Seismic - 12 in. (304 mm)
4) Do not install the UPS in a location that is
subject to high humidity. Also, do not install
the unit in areas that are exposed to direct
sunlight, or contaminated areas subject to
high levels of airborne dust, metal particles, or
flammable gasses.
5) Verify the ventilation and air conditioning
system at the site is capable of removing the
heat generated by the UPS.
Ambient temperature range for operating the
UPS is 32 – 104 °F (0 – 40 °C); 77 °F
(25 °C) is the recommended operating
temperature for maximum battery life.
6) Avoid installation near sources of electrical
noise. Always make sure that the unit's
ground is intact to prevent electrical shock
and help prevent electrical noise.
7) This UPS generates and radiates radio-frequency
energy during operation. Although RFI noise filters
are installed inside the unit there is no guarantee
that the UPS will not influence some sensitive
devices, which are operating in near proximity. If
such interference occurs, the UPS should either
be installed farther away from the affected
equipment and/or powered from a different source
than the affected equipment.
4200FA Installation and Operation Manual
REAR
15-30 kVA Premium – 6 in. (152 mm)
15-30 kVA Base – 12 in. (304 mm)
50 kVA Premium – 12 in. (304 mm)
25/50 kVA Seismic – 12 in. (304 mm)
LEFT
6 in.
(152 mm)
FRONT
20 in. (500 mm)
Fig 3.1
RIGHT
6 in.
(152 mm)