Figure 4-20 External Signal Input Terminal Block (With Default Settings) - Toshiba G2020 Series Installation And Operation Manual

480/480 v 500kva/750kva
Hide thumbs Also See for G2020 Series:
Table of Contents

Advertisement

See Figure 4-20, and Table 4-1.
TN1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
UPS

Figure 4-20 External Signal Input Terminal Block (with default settings)

NOTE:
For multiple battery cabinets, the UVR signals must be connected in parallel with UPS TN1-1 &-2.
For multiple battery cabinets, the Auxiliary Switches must be wired in series with UPS TN1-3 & -4.
* UVR is required for proper operation of system. If the UVR is not present or it is not
properly installed, the system warranty is voided. If you encounter this condition, stop and
do not continue with start-up. (See Figure 4-20 and Figure 5-4 for connection.)
CAUTION
The input logic can be reversed by setting the Active Level to "Neg" when selecting the input function.
This will be annunciated on the Setup screen for the inputs by an "R" next to the Input Port.
For Example:
"IN1
1" indicates the UPS will remote start when contact closes.
"IN1 R1" indicates the UPS will remote start when contact opens.
In all cases, a switch having a protective cover is recommended in order to reduce the
possibility of accidental operation.
CAUTION
G2020 Series UPS Installation and Operation Manual – 94861-004
TN1
+
1(+)-2(-) CB2 UVR* (Battery Breaker)
3-4
CB2 AX (Battery Breaker Panel)
5-6
52L AX (Load Circuit Switch)
7-8
IN1: REMOTE INVERTER START
9-10
IN2: REMOTE INVERTER STOP
11-12
IN3: BATTERY TEMP. HIGH
13-14
IN4: POWER DEMAND
15-16
REMOTE EPO
17-18
N/A
19-20
N/A
Setting
Remarks
User supplied
dry contact
29