4.2 Control Circuit and External Battery Interface Connections 15/25/30 kVA
The following illustrates the wiring connections of the Control Circuits, and Battery Interface
Circuits.
NOTE: Control circuit wiring should be routed in its own conduit. Do not route control circuit wiring
through conduit containing UPS power cables.
(These terminals not available on Base units)
(1) Low Battery
(2) Battery Discharge
(3) Fault
(4) Not Used
(5) Inverter Supply
(6) Inverter Supply
(7) 24Vdc – 1A max. (P24A3)
(8) Remote Run (Switch UPS to Inverter Mode)*
(9) 24Vdc – 1 A max. (P24A3)
(10) Remote Stop (Switch UPS to Static Bypass)*
(11) Bypass
(12) COMMON
(13) EPO (24Vdc – 1A max.)
(14) EPO (24Vdc – 1A max.)
(15) – (24) Not Used
*Must be programmed in via the front panel
4200FA Installation and Operation Manual
(These terminals on ALL units)
Battery Connection
(3) Battery Shunt Trip
(+) Positive
(4) Battery Shunt Trip
(5) Battery Aux.
(-) Negative
(6) Battery Aux.
23