Installation Planning Guide for 15-80kVA UPS
Standard System: 208v (Isolation Xfmr.) Input, 208/120V Output
For Maximum cable sizes, see Note 7.
UPS kVA/ kW Rating
15 kVA/12 kW
25 kVA/ 20 kW
30 kVA/ 24 kW
50 kVA/ 40 kW
Maximum Input Power
Demand
kVA
PF
Amps
15
>0.97
47
25
>0.97
72
30
>0.97
87
50
>0.97
140
Optional Alternate AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
kVA
Amps
15
42
25
67
30
81
50
138
Battery Capacity Required
Maximum Discharge
for Full Load Output
kVA
kWB
15
15
25
24
30
29
50
47
Rated Output Power
kVA
PF
Amps
15
0.8
42
25
0.8
69
30
0.8
83
50
0.8
139
4200FA Installation and Operation Manual
General Mechanical Information
Dimensions
(W x D x H)
Inches
20 x 36.3 x 59.7
20 x 36.3 x 59.7
20 x 36.3 x 59.7
35.5 x 38.3 x 59.3
Primary AC Input (208V 3-Phase / 3-Wire)
Suggested External Feeder
Breaker
Amps
60 A
90 A
110 A
175 A
Suggested External Feeder
Breaker
Amps
60 A
90 A
110 A
175 A
Battery Input (288VDC Nominal)
Suggested External
at Full Load Output
Feeder Breaker
Amps DC
Amps
64
70 A
105
110 A
126
150 A
204
225 A
AC Output (208/120V 3-Phase / 4-Wire)
Suggested External Feeder
Breaker
Amps
60 A
90 A
110 A
175 A
Weight
Lbs.
783
793
798
1,581
Suggested Minimum Feeder
Wire Size Per Phase
AWG or kcmil at 75º C Temp. Rating
(1) x 6
(1) x 3
(1) x 1
(1) x 2/0
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
AWG or kcmil at 75º C Temp. Rating
(1) x 6 / (1) x 4
(1) x 3 / (1) x 1
(1) x 1/ (1) x 1
(1) x 3/0 / (1) x 250
Suggested Minimum Feeder
Wire Size Per Phase
AWG or kcmil at 75º C Temp. Rating
(1) x 4
(1) x 1
(1) x 1
(1) x 250
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
AWG or kcmil at 75º C Temp. Rating
(1) x 6 / (1) x 4
(1) x 3 / (1) x 1
(1) x 2 (1) x 3/0
(1) x 2/0 / (1) x 250
Approximate Full-Load
Heat Loss
kBTU's / Hr
6.4
9.1
12.8
21.3
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
70
70
70
70
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
81