4200Fa 50Kva @ 208 Vac Input/ 208 Vac Output W/Internal Batteries - Toshiba 4200FA Installation And Operation Manual

Three-phase 15/25/30/50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

5.8

4200FA 50kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries

Model Number
Rated Output Capacity
External Dimensions
W x D x H (cm)
Input
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables Required
Dual Input Option Cables required
Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
Harmonic Currents
Battery
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
Rated Back-up Time
Rated Charge Current
Output
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 ms)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
Inrush Current protection
Environment
Efficiency (Typical)
Heat loss to be removed
Audible Noise
Operating Temperature
Operating Humidity
3
Altitude
1 – Specified at rated conditions under balanced linear loads.
2 – Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site. An initial
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
3 – At 6600 ft. (2000 m) above sea level, output capacity should be derated by 3% (Consult factory for higher elevations).
4 – Prolonged operation at this level requires derating of the maximum Operating Temperature to 90 °F ( 32 °C).
5 – SHORT TERM operation only (e.g. Brownouts). Operation at this level requires derating the maximum Operating Temperature to 95 °F ( 35 °C).
40
4,5
1
1
2
Automatic Transfer to bypass, then retransfer to inverter
T42F3F500XAXBN
T42F3F500XAMBN
T42F3F500FAMBN
w/ casters: 35.5" X 38.3" X 59.3" (90.1 cm x 97.2 cm x 150.6 cm)
w/o casters: 35.5" X 38.3" X 59.7" (90.1 cm x 97.2 cm x 151.6 cm)
208 VAC
+10% to -15%; (-10% to -15%)
50 / 60 Hz
3 phase ; 4 Wire + GND
3 phase ; 4 Wire + GND
Greater than 0.98 when in inverter mode
From 20% to 100% over 5 seconds
Less than 8 times the rated current under synchronous operation
115% maximum
Less than 3% THD
288 VDC (216 to 332 VDC)
324.0 VDC (± 2%)
0.5 V R.M.S.
4.5 min. at full load
11.5 Amps
208 / 120 VAC
138.9 Amps
0.8 lagging
3 phase ; 4 Wire + GND
± 2% (0 – 100% balanced load);
± 3% (0 – 100% unbalanced load)
± 5V Manually from key pad
± 2° (0 – 100% balanced load);
± 4° (unbalanced load)
50 / 60 Hz
± 0.1% in free running mode
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.)
switch selectable by qualified technician
1 Hz/s to 3Hz/s(in 0.5 Hz steps)
± 5% (100% load step change);
± 3% (loss or return of input voltage);
± 8% (transfer from bypass to inverter)
125% for 90 sec; 150% for 30 sec
1000% for 10 ms; 125% for 10 min.
2.5 – 3.0 within the kW range
1.73 times line rating
1.5% max (linear load)
AC/DC/AC – See Table 5.10, DC/AC: 89%
See Table 5.10
~65dB @ 1 meter from the front of the unit
32 – 104 °F (0 – 40 °C); optimal temperature is 77 °F (25 °C)
30 – 90% RH (non condensing)
Less than 2000 meters
4200FA Installation and Operation Manual
50 kVA
4
5
, (-15 to -30%)
1
46 kVA
1
2
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4200fa ct

Table of Contents