7
Installation
7.1
Installation Precautions
Install the Slim MBS Cabinet in a controlled environment.
Improper storage and installation environment may deteriorate insulation,
shorten component life and cause malfunctions.
See Table 5.1 - Slim MBS Cabinet Installation Environment Standards
DO NOT tilt the Slim MBS cabinet more than 10° from upright position.
Tilting the Slim MBS Cabinet more than 10° may cause crushing, trapping or
other personal injuries and cause physical damage to internal components.
Keep the SPECIFIED CLEARANCE around the UPS.
Inadequate space around the UPS makes it difficult to perform maintenance/
inspections, will lead to insufficient ventilation, and/or cause malfunctions.
Only factory authorized personnel should relocate, modify, or
replace parts in the Slim MBS Cabinet after initial installation.
Electrical shock, injury or Slim MBS Cabinet failure may occur if non-
authorized technicians attempt to modify or relocate the Slim MBS
Cabinet.
Please contact Toshiba Customer Support Center if you plan to move or
make modifications to the Slim MBS Cabinet
METAL CONDUIT IS NOT AN ACCEPTABLE GROUND.
Conductor Routing and Grounding
1) Use separate metal conduits for routing the input power, output power, and control
circuits.
2) Follow the wire size and tightening torque specifications.
3) Always ground the unit to reduce the potential for electrical shock and to help reduce
electrical noise.
4) A separate ground cable should be run inside the conduit with the input power, output
power, and control circuits.
12
CAUTION
WARNING
WARNING
G9000 Slim MBS Installation and Operation Manual – 96011-000