The D6100IPv6 Ethernet module is a Lantronix Xport Pro with custom firmware installed and
i
UL Listed for use on the D6100IPv6. If standard Lantronix firmware is installed on a
D6100IPv6, the device no longer functions correctly.
12.4.5

Configuring for Network Communication

The following steps allow the D6100IPv6 to communicate with the host computer running the
D6200 Programming Software.
Notice!
For the network communication to function, install a properly configured D6100IPv6. Refer to
i
the previous sections. If network communications are not installed, further D6200 software
programming using the network is not possible.Consequences
1.
Notice!
To change any programming parameter, follow this syntax:
i
Press Enter.
Enter the desired value.
Press Enter again to store the value.
2.
3.
Bosch Security Systems, Inc.
Config
Default
Parameter
Value
aes key
01020304
05060708
09101112
13141516
reboot
enable
Click Save XML As to save the changes, and then enter a name for these configuration
settings.
Click Send XML to send these changes to the D6100IPv6. The device saves the changes
and reboots with the new configuration.
Disconnect the Ethernet cable connecting the computer and the D6100IPv6, and then
connect the D6100IPv6 to the network switch or router as required.
On the D6100IPv6 keypad, press Menu and enter the default passcode of [6][1][0][0] to
enter the programming mode. Press Menu again.
Press Down until viewing 6 NETWORK CONFIGURATION, and then press Enter.
Press Down until viewing 6.2 Network adapter, and then press Enter.
Installation and Operation Guide
Valid Values
Description
16 to 32
Enter the 16 to 32 Hexadecimal characters
Hexadecimal
depending upon the Key size entered:
characters
128-bit requires 16 Hex characters
192-bit requires 24 Hex characters
256-bit requires 32 Hex characters
enable, disable DO NOT CHANGE. This instructs the module
to reboot after the parameters are loaded
into the device to begin using the new
configuration. Eliminates the need to cycle
power to the device. If this is changed from
enabled, it will require a power cycle for the
new configuration to take effect.
Network Communications | en